E47 Inverter Pcb A/F Module Anomaly (Model Fdc 71 Only) - Mitsubishi Electric FDF100VSXVD Technical Manual

Hide thumbs Also See for FDF100VSXVD:
Table of Contents

Advertisement

Error code
E47
Remote controller:
Outdoor control PCB
1. Applicable model
Model FDC71
2. Error detection method
In order to prevent from
overcurrent of A/F, if the current
makes the compressor stopping.
3. Condition of error displayed
• If the output current of A/F
it makes the compressor
stopping.
4. Presumable cause
• Defective inverter PCB
Note:
LED
Green
Indoor
Keeps flashing
Keeps flashing
Outdoor
Yellow LED or Red LED Green LED
Inverter
7 times flashing
PCB
5. Troubleshooting
Power supply
voltage OK?
checked results of
insulation resistance and
coil resistance (1) of
compressor motor
Red
Content
Stays off
1 time flash
Inverter PCB A/F module anomaly
Diagnosis
Is the
YES
Is the
OK?
(1) 1.154 or more at 20°C (FDC71)
YES
185
'11 • PAC-T-160
(Model FDC71 only)
Countermeasure
Check power supply.
NO
Replace compressor.
NO
Defective outdoor Inverter
PCB Replace.