Trial operation (Continued)
Checking operation data
Operation data can be checked with remote
control unit operation.
1. Press the
button.
The display change "
"
2. Press the
(SET) button while
"
" is displayed.
When only one indoor unit is connected to
remote controller, "
" is
displayed (blinking indication during data
loading).
Next, operation data of the indoor unit
will be displayed. Skip to step 7.
4. When plural indoor units is connected, the
smallest address number of indoor unit
among all connected indoor unit is displayed.
[Example]:
"
" (blinking 1 seconds)
"
" blinking.
5. Select the indoor unit number you would
like to have data displayed with the
button.
6. Determine the indoor unit number with the
(SET) button.
(The indoor unit number changes from blinking indication to continuous indication)
"
" (The address of selected indoor unit is blinking for 2 seconds.)
"
" (A blinking indication appears while data loaded.)
Next, the operation data of the indoor unit is indicated.
7. Upon operation of the
button, the current operation data is displayed in order from data
number 01.
The items displayed are in the above table.
Depending on models, the items that do not have corresponding data are not displayed.
8. To display the data of a different indoor unit, press the
the indoor unit selection screen.
9. Pressing the
button will stop displaying data.
Pressing the
(RESET) button during remote control unit operation will undo your last operation and
allow you to go back to the previous screen.
If two (2) remote controllers are connected to one (1) inside unit, only the master controller is available for trial
operation and confirmation of operation data. (The slave remote controller is not available.)
Control mode switching
The control content of indoor units can be switched in following way.
(
is the default setting)
Switch No.
Control Content
SW2
Indoor unit address (0-Fh)
SW5-1
Master/Slave Switching (plural /Slave unit Setting)
SW5-2
Model capacity setting
SW6-1 4
ON
Operation check, Drain motor test run
SW7
1
OFF
Normal operation
Function of CNT connector of indoor printed circuit board
Note (1) 0.3 mm
Indoor units
Do not use the length over 2 meter
control box
+12
Red
1
1
Black
2
2
XR1
CNT
Yellow
3
3
XR2
(Blue 6P)
Blue
4
4
XR3
Brown
5
5
XR4
Orange
6
6
PCB (Printed Circuit Board)
CNT connector (local) vendor model
Connector : Made by molex 5264 - 06
Terminals : Made by molex 5263T
Function
Output 1
Operation output (there is output when unit is in operation.)
Output 2
Heating output (there is output when operation MODE is HEATING.)
Output 3
Compressor ON output (there is output when compressor is in operation.)
Output 4
Inspection output (there is output when unit is stopped by error.)
Input 5
Remote operation input (Volt-free contact) (Inputted to operate unit)
Number
Data Item
01
(Ope ration Mode)
02
(Set Temperature)
03
(Return Air Temperature)
04
(Remote Controller ThermistorTemperature)
05
(Indoor Unit Heat Exchanger Thermistor / U Bend)
06
(Indoor Unit Heat Exchanger Thermistor /Capillary)
07
(Indoor Unit Heat Exchanger Thermistor /Gas Header)
08
(Indoor Unit Fan Speed)
09
(Frequency Requirements)
10
(Response Frequency)
11
(Pulse of Indoor Unit Expansion Value)
12
(Total Running Hours of The Indoor Unit)
21
(Outdoor Air Temperature)
22
(Outdoor Unit Heat Exchanger Thermistor)
23
(Outdoor Unit Heat Exchanger Thermistor)
24
(Compressor Frequency)
25
(High Pressure)
26
(Low Pressure)
27
(Discharge Pipe Temperature)
28
(Comp Bottom Temperature)
29
(Current)
30
(Target Super Heat)
31
(Super Heat)
32
(Discharge Pipe Super Heat)
33
(Protection State No. of The Compressor)
34
(Outdoor Unit Fan Speed)
35
(63H1 On/Off)
36
(Defrost Control On/Off)
37
(Total Running Hours of The Compressor)
38
(Pulse of The Outdoor Unit Expansion Valve EEVC)
39
(Pulse of The Outdoor Unit Expansion Valve EEVH)
Depending on outdoor unit model, there are data not shown.
button, which allows you to go back to
2
×2m
0.75 mm
2
×0.2m
Butt splice
(Application coverage
2
0.75 1.25mm
)
White
Common
Black
XR1
Output 1
Yellow
XR2
Output 2
XR3
Blue
Output 3
Brown
XR4
Output 4
Orange
XR5
Input
Orange
power
Remote start / stop button or timer point
Remote start/stop kit
Troubleshooting
The operation data is saved when the situation of abnormal operation happen, and the data
can be confirmed by remote controller.
Error Code of indoor unit
Display on
LED on indoor circuit board
remote
red (checking)
controller
Off
Off
Off
Off
E1
Not sure
Blinking twice
E5
E6
Blinking once
E7
Blinking once
E8
Blinking once
Blinking once
E9
E10
Off
E14
Blinking for three times
E16
Blinking once
E19
Blinking once
E28
Off
Off
Over E30
[Operating procedure]
1. Press the
button.
The display change "
2. Once, press the
button, and the display change
"
".
3. Press the
(SET) button and abnormal operation data mode is started.
4. When only one indoor unit is connected to remote controller, following is displayed.
The case that there is history of abnormal operation.
Error code and "
[Example]: [E8] (ERROR CODE)
"
" is displayed (blinking indication during data loading).
Next, the abnormal operation data of the indoor unit will be displayed. Skip to step 8.
The case that there is not history of abnormal operation.
"
" is displayed for 3 seconds and this mode is closed.
5. When plural indoor units is connected, following is displayed.
The case that there is history of abnormal operation.
Error code and the smallest address number of indoor unit among all connected indoor
unit is displayed.
[Example]: [E8] (ERROR CODE)
"
" blinking
The case that there is not history of abnormal operation.
Only address number is displayed.
6. Select the indoor unit number you would like to have data displayed with the
button.
7. Determine the indoor unit number with the
[Example]: [E8] (ERROR CODE)
"
" (The address of selected indoor unit is blinking for 2 seconds.)
[E8] "
" (A blinking indication appears while data loaded.)
Next, the abnormal operation data is indicated.
If the indoor unit doing normal operation is selected, "
seconds and address of indoor unit is displayed.
8. By the
button, the abnormal operation data is displayed.
Displayed data item is based on
Depending on models, the items that do not have corresponding data are not displayed.
9. To display the data of a different indoor unit, press the AIR CON No. button, which allows
you to go back to the indoor unit slection screen.
10.Pressing the
button will stop displaying data.
Pressing the
(RESET) button during remote control unit operation will undo your last
operation and allow you to go back to the previous screen.
If two (2) remote controllers are connected to one (1) indoor unit, only the master controller
is available for trial operation and confirmation of operation data. (The slave remote control-
ler is not available.)
-
-
63
63
-
-
'11 • PAC-T-160
Content
green (normal)
Continuous blinking
Normal
Fault on power, indoor power off or lack
Off
phase
Fault on the transmission between
Continuous blinking
indoor circuit board and remote control
Indoor computer abnormal
Not sure
Continuous blinking
Fault on outdoor-indoor transmission
Indoor heat exchange sensor interrupted or
Continuous blinking
short-circuit
Indoor air inhaling sensor broken or
Continuous blinking
short-circuit
The temperature of heat exchange
Continuous blinking
abnormal
Continuous blinking
Float SW actions (only with FS)
Excess number of remote controller
Continuous blinking
connections
The communication fault for master/slave
Continuous blinking
indoor units
Continuous blinking
Fan motor abnormal
Configuration fault on running checking
Continuous blinking
model
Remote controller sensor interrupted
Continuous blinking
Outdoor unit checking (outdoor circuit board
Continuous blinking
LED checking)
"
" is displayed.
(SET) button.
" is displayed for 3
Trial operation