Mitsubishi Electric FDF100VSXVD Technical Manual page 161

Hide thumbs Also See for FDF100VSXVD:
Table of Contents

Advertisement

Error code
WAIT
Remote controller:
All models
• Faulty noise filter
• Faulty indoor control PCB
• Faulty outdoor control PCB
• Faulty inverter PCB
• Faulty fan motor
Note:
L E D
G r een
Red
Stays OFF
Indoor
Outdoor
Diagnosis
Diagnosis for when the outdoor
control PCB LED is turned off
From Previous page
A
Shut down the breaker and back on
again the breaker 3 minutes later.
NO
Does it reset normally?
Isn't the outdoor
unit controller power supply fuse
(30A) blown?
To check method for inverter PCB before
replacment of blown power supply fuse.
YES
Is AC220/240V
detected at the noise filter
secondary side?
YES
Model 71-140
Is DC255-310V detected at CNA2?
Model 200, 250 Is 220/240
detected at CNW2?
YES
Isn't fuse
〔250V, 2(3)A〕 on the outdoor control
PCB blown?
YES
Is DC5V
detected on the outdoor control PCB (Between
- of CNI1)?
YES
Is DC5V detected
if the connector of outdoor unit fan motor
is disconnected?
YES
Is DC5V detected
if the inverter power supply connector (CNI2)
is disconnected?
-
160
Content
Communication error at
initial operation (2/3)
Note (1) 1-phase model only
(1)
NO
To next page
B
NO
NO
Note (2) Value in ( ) are for the
model 200, 250.
(2)
NO
NO
NO
NO
YES
-
'11 • PAC-T-160
Normal (Malfunction by
noise)
Check connection of diode
stack and electrolytic
capacitor by refering main
electrical circuit diagram
Defective outdoor fan
motor
Defective inverter PCB
Replace.
Defective outdoor control
PCB Replace.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents