E6 Indoor Heat Exchanger Temperature Thermistor Anomaly - Mitsubishi Electric FDF100VSXVD Technical Manual

Hide thumbs Also See for FDF100VSXVD:
Table of Contents

Advertisement

Error code
E6
Remote controller:
1. Applicable model
All models
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected on the indoor heat
exchanger thermistor (ThI-R1,
R2 or R3).
3. Condition of Error displayed
• When the temperature
thermistor detects -50°C
or lower for 5 seconds
continuously, the compressor
stops. After 3-minutes delay,
the compressor starts again
automatically, but if this
error occurs again within
60 minutes after the initial
detection.
• Or if 70°C or higher is
detected for 5 seconds
continuously.
4. Presumable cause
• Defective indoor heat
exchanger thermistor
connector
• Indoor heat exchanger
temperature thermistor
anomaly
• Faulty indoor control PCB
Note:
L E D
G r een
Red
Indoor
Stays OFF
Outdoor
5. Troubleshooting
Diagnosis
Is the
connection of indoor heat
exchanger temperature thermistor
connector OK?
YES
Are
characteristics of indoor
heat exchanger temperature
thermistor OK?
Temperature-resistance characteristic
(Broken wire)
15
10
5
(Shot circuit)
0
10
Temperature (°C)
-
165
Content
Indoor heat exchanger
temperature thermistor anomaly
NO
NO
YES
°C
5k at 25
20
30
40
50
-
'11 • PAC-T-160
Countermeasure
Correct.
Insert connector
securely.
Defective indoor heat
exchanger temperature
thermistor
Replace.
Defective indoor control
PCB
Replace.
(Defective indoor unit heat
exchanger temperature
thermistor input circuit)