Range Of Usage & Limitations - Mitsubishi Electric FDF100VSXVD Technical Manual

Hide thumbs Also See for FDF100VSXVD:
Table of Contents

Advertisement

7. RANGE OF USAGE & LIMITATIONS
Operating temperature range
Recommendable area to install
Installation site
Temperature and humidity conditions surrounding the
indoor unit
Limitations on unit and piping installation
Cycle Time
Compressor
ON-OFF cycling
Stop Time
Voltage range
Power source
Voltage drop at start-up
Phase-to-phase imbalance
Note 1. Do not install the unit in places which :
1) Flammable gas may leak.
2) Carbon fiber, metal particles, powder, etc. are floating.
3) Cosmetic or special sprays are used frequently.
4) Exposed to oil splashes or steam (e.g. kitchen and machine plant).
5) Exposed to sea breeze (e.g. coastal area) or calcium chloride (e.g. snow melting agent).
6) Exposed to ammonia substance (e.g. organic fertilizer).
7) Matters affecting devices, such as sulfuric gas, chlorine gas, acid, alkali, etc. may generate or accumulate.
8) Chimney smoke is hanging.
9) Sucking the exhaust gas from heat exchanger.
10) Adjacent to equipment generating electromagnetic waves or high frequency waves.
11) There is light beams that affect the receiving device of indoor unit in case of the wireless specification.
12) Snow falls heavily.
13) At an elevation of 1000 meters or higher.
14) On mobile machine (e.g. vehicle, ship, etc.)
15) Splashed with water to indoor unit (e.g. laundry room).
16) Indoor units of twin, triple and double-twin specifications separately in a room with partition.
Note 2. Both gas and liquid pipes need to be coverd with 20mm or thicker heat insulation materials at the place where humidity exceeds 70%.
When used below -5˚C, install a snow hood (option)
Considering to get sufficient heating capacity, the area where the averaged lowest ambient
air temperature in day time during winter is above 0˚C, and it has no accumulation of snow.
The limitations of installation space are shown in the page for exterior dimensions.
Dew point temperature : 23˚C or less, relative hummdity : 80% or less
7 minutes or more (from OFF to OFF) or (from ON to ON)
-
41
-
See next page.
See page
43
3 minutes or more
Rating ±10%
Min.85% of rating
3% or less
PGA000Z784
'11 • PAC-T-160
A

Hide quick links:

Advertisement

Table of Contents