E14 Communication Error Between Master And Slave Indoor Units - Mitsubishi Electric FDF100VSXVD Technical Manual

Hide thumbs Also See for FDF100VSXVD:
Table of Contents

Advertisement

Error code
Remote controller:
E14
1. Applicable model
All models
2. Error detection method
When communication error
between master and slave indoor
units occurs
3. Condition of Error displayed
Same as above
4. Presumable cause
• Unit address setting error
• Broken remote controller wire
• Defective remote controller
wire connection
• Defective indoor control PCB
Note:
L E D
G r een
Red
Indoor
Keeps flashing 3 times flash
Outdoor
Keeps flashing Stays Off
5. Troubleshooting
Diagnosis
OK the unit
address setting for master
and slave indoor
the remote
controller wiring between
indoor units
defective?
restored by resetting the
power supply?
Note (1) Set dip switches SW5-1 and SW5-2 as shown in the following table.
(Factory default setting – "Master")
Master
SW5-1
OFF
Dip
switch
SW5-2
OFF
-
169
Content
Communication error
between master and slave indoor units
Is it
NO
units?
YES
Isn't
YES
NO
Is it
NO
YES
Indoor unit
Slave-a
Slave-b
Slave-c
OFF
ON
ON
ON
OFF
ON
-
'11 • PAC-T-160
Countermeasure
Correct unit address setting.
Correct wiring.
Defective indoor control
PCB Replace.
• Malfunction by noise
• Check surrounding
environment.