Stat-X Aerosol Generators - Honeywell NOTIFIER RP-2002C Instruction Manual

Agent release panel
Table of Contents

Advertisement

Installation

Stat-X Aerosol Generators

Figure 2.9 shows typical wiring for Stat-X devices using the Ematch Protection Device
(P/N 3005014).
Notes:
1.
Each Stat-X device requires an Ematch Protection Device to protect against high voltage
transient signals, such as lightning, that may cause the device to accidentally release.
2.
Multiple Stat-X devices can be connected in series (as shown).
3.
No more than ten (10) Stat-X devices can be connected on a single releasing circuit.
4.
An REL-4.7K can be installed on a single Stat-X device for short circuit detection. for multiple
Stat-X devices installed in series, the REL-4.7K is installed on the last device on the releasing
circuit (as shown). An REL-4.7K is required for ULC applications.
28
+
Releasing Circuit
-
green
yellow
black
red
Figure 2.9 Wiring Stat-X Devices
Ematch Protection
Device (P/N 3005014)
REL-4.7K
RP-2002 Series Manual — P/N 53039:E6 1/26/2017