B.10: Template 10: Dual Hazard - Single Detector - Honeywell NOTIFIER RP-2002C Instruction Manual

Agent release panel
Table of Contents

Advertisement

FACP Configuration Templates
B.10 Template 10: Dual Hazard - Single Detector
OUTPUT CIRCUITS
#1 RELEASE CIRCUIT 1
#2 RELEASE CIRCUIT 2
#3 RELEASE STAGE
CODED
#4 RELEASE STAGE
CODED
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).
Xr = release stage output where X indicates a direct correlation between Input Zone and Output
Circuit (input zone activation will activate the corresponding output circuit) and r indicates that the
output circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to
"Release Stage/NAC Operation" on page 85).
Input Zone Types:
Zone 1 = circuit with type code of 2-wire smoke
Zone 2 = circuit with type code of 2-wire smoke
Zone 3 = circuit with type code Manual Release/Abort Switch Combination - activation of the
Manual Release will cause an immediate agent release; Abort Switch - programmed for UL
Abort Type operation (refer to "Abort Type" on page 65)
Zone 4 = circuit with type code of 2-wire smoke
Zone 5 = circuit with type code of 2-wire smoke
Zone 6 = circuit with type code Manual Release/Abort Switch Combination - activation of the
Manual Release will cause an immediate agent release; Abort Switch - programmed for UL
Abort Type operation (refer to "Abort Type" on page 65)
Output Circuit Types:
Output 1 = Release Circuit 1 - Supervised for shorts
Output 2 = Release Circuit 2 - Supervised for shorts
Output 3 = Release Stage Coded - silenceable, programmed Release Stage Coded operation for
Release Circuit 1 (refer to "Cross-Zone for Release Circuit 1 or Release Circuit 2:" on
page 61)
Output 4 = Release Stage Coded - silenceable, programmed Release Stage Coded operation for
Release Circuit 2 (refer to "Cross-Zone for Release Circuit 1 or Release Circuit 2:" on
page 61)
Timers
Pre-Discharge Delay: Release 1 - set for 30 seconds; Release 2 - set for 30 seconds
Discharge: Release 1 - set for Always On; Release 2 - set for Always On
Waterflow Delay Timer - set for 90 seconds
AC Loss Delay Timer - set for 2 hours
128
Template 10: Dual Hazard - Single Detector
1
2
2-WIRE
2-WIRE
RELEASE/ABORT
SMOKE
SMOKE
SW. COMBO
X
X
Xr
Xr
Template 10: Dual Hazard - Single Detector
INPUT ZONES
3
4
MANUAL
2-WIRE
SMOKE
X
X
Xr
Xr
RP-2002 Series Manual — P/N 53039:E6 1/26/2017
5
6
MANUAL
2-WIRE
RELEASE/ABORT
SMOKE
SW. COMBO
X
X
Xr
Xr

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier rp-2002Notifier rp-2002eNotifier rp-2002 series

Table of Contents