Specifications - Honeywell NOTIFIER RP-2002C Instruction Manual

Agent release panel
Table of Contents

Advertisement

Product Description
Fire Alarm
Supervisory
Trouble
AC Power
Alarm Silenced
Discharge
Pre-Discharge
Abort
Piezo sounder for alarm, trouble and supervisory
24 volt operation
Low AC voltage sense
Outputs Programmable for:
Releasing Solenoids
NACs programmable for:
– Silence Inhibit
– Auto-Silence
– Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)
– Selective Silence (horn-strobe mute)
– Temporal or Steady Signal
– Silenceable or Nonsilenceable
– Release Stage Sounder
Designed for agent releasing standards NFPA 12, 12A, and 2001
Disable/Enable control per input zone and output zone
Extensive transient protection
Dual hazard operation
Adjustable pre-discharge, discharge and waterflow delay timers
Cross-zone (double-interlock) capability
Pre-programmed and custom application templates
Programmable Abort operation
Automatic battery charger with charger supervision
Silent or audible walktest capabilities
Optional Dress Panel DP-51050 (red)
A modified Dress Panel is provided standard with Canadian models: includes an N-ANN-LED
Annunciator module
Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet
Optional N-CAC-5X Class A Converter Module for Outputs and IDCs
Optional 4XTM Municipal Box Transmitter Module
Optional Digital Alarm Communicators (411, 411UD, 411UDAC)
Optional ANN-SEC card for a secondary ANN-BUS

1.2 Specifications

AC Power
RP-2002/C: 120 VAC, 60 Hz, 3.66 amps
RP-2002E: 240 VAC, 50/60 Hz, 2.085 amps
Wire size: minimum #14 AWG (2.0 mm
Supervised, nonpower-limited
14
2
) with 600V insulation
RP-2002 Series Manual — P/N 53039:E6 1/26/2017
Specifications

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier rp-2002Notifier rp-2002eNotifier rp-2002 series