B.8: Template 8: Single Hazard, Single Detector - Bell/Horn/Strobe - Honeywell NOTIFIER RP-2002C Instruction Manual

Agent release panel
Table of Contents

Advertisement

FACP Configuration Templates
B.8 Template 8: Single Hazard, Single Detector -
Bell/Horn/Strobe
Template 8: Single Hazard, Single Detector - Bell/Horn/Strobe
OUTPUT CIRCUITS
#1 RELEASE CIRCUIT 1
#2 ALARM NAC
#3 RELEASE STAGE
CODED
#4 RELEASE STAGE
DISCHARGE
Table Legend:
* = shows relationship only, will not activate a release circuit
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).
Xr = release stage output where X indicates a direct correlation between Input Zone and Output
Circuit (input zone activation will activate the corresponding output circuit) and r indicates that the
output circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to
"Release Stage/NAC Operation" on page 85).
Input Zone Types:
Zone 1 = circuit with type code of 2-wire smoke
Zone 2 = circuit with type code of 2-wire smoke
Zone 3 = circuit with type code Manual Release - activation will cause an immediate agent
release
Zone 4 = circuit with type code of Abort Release Switch - programmed for UL Abort Type
operation (refer to "Abort Type" on page 65)
Zone 5 = circuit with type code of Discharge Pressure Switch
Zone 6 = circuit with type code of Supervisory
Output Circuit Types:
Output 1 = Release Circuit 1 - Supervised for shorts
Output 2 = Alarm NAC - silenceable, programmed for Cross-Zone Discharge coded operation
for Release Circuit 1 (refer to "Cross-Zone for Release Circuit 1 or Release Circuit 2:" on
page 61)
Output 3 = Release Stage Coded - non-silenceable, programmed Release Stage Coded
operation for Release Circuit 1 (refer to "Cross-Zone for Release Circuit 1 or Release Circuit
2:" on page 61)
Output 4 = Release Stage Discharge - nonsilenceable, programmed Release Stage Discharge
operation for Release Circuit 1 (refer to "Cross-Zone for Release Circuit 1 or Release Circuit
2:" on page 61)
Timers
Pre-Discharge Delay - set for 30 seconds
Discharge - set for Always On
Waterflow Delay Timer - set for 90 seconds
122
1
2
2-WIRE
2-WIRE
SMOKE
SMOKE
X
X
X
X
Xr
Xr
Xr
Xr
Template 8: Single Hazard, Single Detector - Bell/Horn/Strobe
INPUT ZONES
3
4
MANUAL
DISCHARGE
ABORT
RELEASE
PRESSURE
X
X*
Xr
Xr
RP-2002 Series Manual — P/N 53039:E6 1/26/2017
5
6
SUPERVISORY
X*
Xr
Xr