Section 5: Power Supply Calculations; Overview; Calculating The Ac Branch Circuit - Honeywell NOTIFIER RP-2002C Instruction Manual

Agent release panel
Table of Contents

Advertisement

Section 5: Power Supply Calculations

5.1 Overview

This section contains instructions and tables for calculating power supply currents in alarm and
standby conditions. This is a four-step process, consisting of the following:
1.
Calculating the total amount of AC branch circuit current required to operate the system
2.
Calculating the power supply load current for non-fire and fire alarm conditions and
calculating the secondary (battery) load
3.
Calculating the size of batteries required to support the system if an AC power loss occurs
4.
Selecting the proper batteries for your system

5.2 Calculating the AC Branch Circuit

The control panel requires connection to a separate, dedicated AC branch circuit, which must be
labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed of
the protected premises. No other non-fire alarm equipment may be powered from the fire alarm
branch circuit. The branch circuit wire must run continuously, without any disconnect devices,
from the power source to the control panel. Overcurrent protection for this circuit must comply
with Article 760 of the National Electrical Codes as well as local codes. Use 14 AWG (2.00 mm
wire with 600 volt insulation for this branch circuit.
Use Table 5.1, to determine the total amount of current, in AC amperes (A), that must be supplied
to the system.
Device Type
RP-2002/C
or
RP-2002E
RP-2002 Series Manual — P/N 53039:E6 1/26/2017
Number of
Devices
1
X
[
]
X
[
]
X
Sum Column for AC Branch Current Required
Table 5.1 Branch Circuit Requirements
Current Draw
(AC amps)
3.66
=
or
2.085
[
]
=
[
]
=
=
2
)
Total Current
per Device
91

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier rp-2002Notifier rp-2002eNotifier rp-2002 series

Table of Contents