FACP Configuration Templates
B.2 Template 2: Single Zone System With Horn
OUTPUT CIRCUITS
#1 RELEASE CIRCUIT 1
#2 RELEASE STAGE NAC
#3 ALARM NAC
#4 ALARM NAC
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).
Xr = release stage output where X indicates a direct correlation between Input Zone and Output
Circuit (input zone activation will activate the corresponding output circuit) and r indicates that the
output circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to
"Release Stage/NAC Operation" on page 85).
Input Zone Types:
Zone 1 = circuit with type code of 2-wire smoke
Zone 2 = circuit with type code of 2-wire smoke
Zone 3 = circuit with type code Manual Release - activation will cause an immediate agent
release
Zone 4 = circuit with type code of Abort Release Switch - programmed for UL Abort Type
operation (refer to "Abort Type" on page 65)
Zone 5 = circuit with type code of Pull Station
Zone 6 = circuit with type code of Supervisory
Output Circuit Types:
Output 1 = Release Circuit 1 - Unsupervised for shorts
Output 2 = Release Stage NAC - silenceable, programmed Release Stage operation (refer to
"Release Stage/NAC Operation" on page 85)
Output 3 = Alarm NAC - silenceable, coded for steady on
Output 4 = Alarm NAC - silenceable, coded for steady on
Timers
Pre-Discharge Delay - set for 30 seconds
Discharge - set for 1 minute
Waterflow Delay Timer - set for 90 seconds
AC Loss Delay Timer - set for 2 hours
104
Template 2: Single Zone System with Horn
1
2
2-WIRE
2-WIRE
SMOKE
SMOKE
X
X
Xr
Xr
X
X
Template 2: Single Zone System With Horn
INPUT ZONES
3
4
MANUAL
ABORT
RELEASE
STATION
X
Xr
X
RP-2002 Series Manual — P/N 53039:E6 1/26/2017
5
6
PULL
SUPERVISORY
X