Abort Type; Timers - Honeywell NOTIFIER RP-2002C Instruction Manual

Agent release panel
Table of Contents

Advertisement

Master Programming Level
PROGRAMMING
Pressing 3 for System Setup, while viewing Programming Screen #2, will cause the following
1=CROSS INPUT ZONES
2=ON-BOARD RELAYS
screens to be displayed:
3=SYSTEM SETUP
Programming Screen #2

1=ABORT TYPE

2=TIMERS

3=BANNER
Abort Type
The Abort function provides the ability to stop an agent release that was initiated by an automatic
detection device. The Abort Type provides the programmer with four abort methods:
NOTE: The Abort functions will not operate if the Pre-discharge Delay timer is set to zero. Also,
activation of a Manual Release Switch will override Pre-discharge Delay and override an active
Abort Release Switch, resulting in an immediate agent release.
Timers
SYSTEM SETUP
1=ABORT TYPE
2=TIMERS
Timers for Pre-discharge, Discharge, Waterflow Delay and AC Loss Delay can be programmed by
3=BANNER
pressing 2 while viewing System Setup Screen #1. The following screens will be displayed:
System Setup Screen #1
There are two Pre-discharge timers which allows each releasing circuit to be programmed with
different pre-discharge delay times. The factory default setting for each Pre-discharge timer is 0 for
no delay. To select a Pre-discharge delay of 01 to 60 seconds, press 1 for Pre-Discharge1 or 2 for
Pre-Discharge2 while viewing Timer Screen #1. The following display will appear:
RP-2002 Series Manual — P/N 53039:E6 1/26/2017
ANN-SECONDARY: This option allows the use of a secondary ANN-BUS with the ANN-SEC
option module. This option must be enabled if the ANN-SEC option card is installed on J13 of
the main circuit board.
SYSTEM SETUP
System Setup Screen #1
UL (UL 864 approved) - A releasing event starts the Pre-discharge timer. If the Abort
Switch is pressed while the Delay Timer continues to count down, the timer counts down to
10 seconds and holds there. If the Abort Switch is released, the timer resumes the
countdown from 10 seconds.
IRI (UL 864 approved)- This Abort Type functions the same way as the UL type, except
that the Abort Switch will not function unless it is pressed before the cross-zoned second
input device activates
NYC - A releasing event starts the Pre-discharge timer. Pressing an Abort switch will stop
the Pre-discharge timer. Releasing the Abort switch resets the Pre-discharge timer to the
original time plus 90 seconds. The Abort switch can be operated multiple times, with each
operation resetting the Pre-discharge timer to the original time plus 90 seconds.
Local Jurisdiction - A releasing event starts the Pre-discharge timer. Pressing an Abort
switch will stop the Pre-discharge timer. Releasing the Abort switch resets the Pre-discharge
timer to the original time. The Abort switch can be operated multiple times, with each
operation resetting the Pre-discharge timer to the original time.
TIMERS
1=PRE-DISCHARGE1 60S
2=PRE-DISCHARGE2 60S
3=DISCHARGE1
Timer Screen #1
Pre-Discharge
SYSTEM SETUP
1=TIME-DATE
2=TROUBLE REMIND
NO
3=CHARGR DISABLE
NO
System Setup Screen #2
TIMERS
1=DISCHARGE2
2=WATERFLW DELAY 90S
1MIN
3=AC LOSS DELAY
Timer Screen #2
PRE-DISCHARGE DELAY
RANGE 00-60 SECONDS
Pre-Discharge Setup Screen
Programming
SYSTEM SETUP
1=CANADIAN OPTIONOFF
2=SEC ANN ENABLE NO
System Setup Screen #3
1MIN
2HR
65