Honeywell NOTIFIER RP-2002C Instruction Manual page 55

Agent release panel
Table of Contents

Advertisement

Master Programming Level
Pressing the down arrow key displays additional zone types as indicated in the following table.
Manual Release/Abort
Normally Open Contact
Waterflow NS (nonsilenceable)
Combo w/AutoResettable Superv
Low Pressure AutoResettable
High Pressure AutoResettable
Supervisory AutoResettable
1 Activation of a Manual Release Switch will override Predischarge Delay and override
an active Abort Release Switch, resulting in an immediate agent release.
2 Discharge Pressure Switch can be mapped to one or both Release Circuits, but it will
not activate them. The following will occur when it is avtivated:
 Alarm LED flashes 1/2 second on, 1/2 second off
 Discharge LED turns on steady
Alarm Relay(s) activate
 Momentarily activate/energize any relay programmed as a pre-discharge relay
 Activate any relay programmed as a discharge relay
 Turn on all enabled and mapped NACs
 Display an active IDC message on FACP display and send message to printer/pc
Turn on FACP piezo
3 AutoResettable means that a device with this type code, when activated, will automat-
ically reset when the corresponding condition is cleared.
4 Disable Release allows the installer to disable the releasing solenoids during system
testing. Disable Release will only work when the system is not in alarm.
5 Activation of an Abort Release Switch during system normal operation (non-alarm)
results in an audible and visual indication at the FACP. If the Abort Switch is pressed
and then the Manual Release is activated, the Manual Release will over-ride the Abort
and cause an immediate release. If Manual Release is activated and then Abort
Switch is pressed, the Abort Switch will have no effect.
While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and
indicate the selection next to the Type option.
RP-2002 Series Manual — P/N 53039:E6 1/26/2017
Zone Type
Pull-Station
1
Manual Release
1
5
,
2
Discharge Pressure
N/A
N/A
N/A
Waterflow
Combo
3
2-Wire Smoke
2-Wire Heat
N/A
Linear Heat
N/A
N/A
Fire
Low Pressure
3
High Pressure
3
4
Disable Release
Supervisory
3
5
Abort Release Switch
N/A
Table 3.1 Zone Types
Action When Activated
Fire Alarm
Fire Alarm
Fire Alarm
Fire Alarm
Fire
Fire
Fire, nonsilenceable
Fire/Supervisory
Fire/Supervisory, nonlatching
Fire Alarm
Fire Alarm
Fire Alarm
Fire Alarm
Supervisory, latching
Supervisory, nonlatching
Supervisory
Supervisory, nonlatching
Supervisory, nonlatching (disables Release Circuits)
Supervisory, latching
Supervisory, nonlatching
Supervisory, nonlatching
Programming
55