Template 10: Dual Hazard - Single Detector
FACP Operation
Input Zone 1 (2-Wire Smoke) Activation only:
Output 1 (Release Circuit 1) will perform an agent release following a 30 second Pre-
Discharge delay and remains on until panel reset.
Output 3 (Release Stage Coded) will pulse 1/2 second on, 1/2 second off until discharge, then
on steady.
Input Zone 2 (2-Wire Smoke) Activation only:
Output 1 (Release Circuit 1) will perform an agent release following a 30 second Pre-
Discharge delay and remains on until panel reset.
Output 3 (Release Stage Coded) will pulse 1/2 second on, 1/2 second off until discharge, then
on steady.
Input Zone 3 (Manual Release) Activation only:
Output 1 (Release Circuit 1) agent release remains on until reset.
Output 3 (Release Stage Coded) will turn on steady.
Input Zone 3 (Abort Release Switch) Activation only:
Pre-Discharge Timer for Release Circuit 1will continue to count down until it reaches 10
seconds and then stop. Releasing the Abort Release Switch will allow the Pre-Discharge Timer
to continue its count down from 10 second. If the Abort Release Switch is again activated
before the Pre-Discharge Timer reaches 0, the Timer will reset to 10 seconds and hold.
Input Zone 4 (2-Wire Smoke) Activation only:
Output 2 (Release Circuit 2) will perform an agent release following a 30 second Pre-
Discharge delay and remains on until panel reset.
Output 4 (Release Stage Coded) will pulse 1/2 second on, 1/2 second off until discharge, then
on steady.
Input Zone 5 (2-Wire Smoke) Activation only:
Output 2 (Release Circuit 2) will perform an agent release following a 30 second Pre-
Discharge delay and remains on until panel reset.
Output 4 (Release Stage Coded) will pulse 1/2 second on, 1/2 second off until discharge, then
on steady.
Input Zone 6 (Manual Release) Activation only:
Output 2 (Release Circuit 2) agent release remains on until reset.
Output 4 (Release Stage Coded) will turn on steady.
Input Zone 6 (Abort Release Switch) Activation only:
Pre-Discharge Timer for Release Circuit 2 will continue to count down until it reaches 10
seconds and then stop. Releasing the Abort Release Switch will allow the Pre-Discharge Timer
to continue its count down from 10 second. If the Abort Release Switch is again activated
before the Pre-Discharge Timer reaches 0, the Timer will reset to 10 seconds and hold.
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
Alarm Relay (Latching) - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (2-Wire
Smoke) or Zone 3 (Manual Release) or Zone 4 (2-Wire Smoke) or Zone 5 (2-Wire Smoke) or
Zone 6 (Manual Release) will operate Alarm Relay
Trouble Relay (Tracking) - any system trouble will activate the Trouble Relay
Supervisory (Tracking) - the disabling of Releasing Circuit or any other system supervisory
will operate the Supervisory Relay
RP-2002 Series Manual — P/N 53039:E6 1/26/2017