Vertiv Liebert EDGE Installer/User Manual page 53

Table of Contents

Advertisement

Table 6.3 Specifications, EDGE-1500IRT2UXL, EDGE-2200IRT2UXL,EDGE-3000IRT2UXL and EDGE-
3000IRT3UXL (continued)
MODEL
Power Rating @ 230V
Output Overload
Operation
Protection
AC-mode Efficiency
Buck- Boost1- and
Boost2- mode
Recharge Time
Internal Battery
Part Number
Protection
Type
Quantity x Voltage x Ah
External Battery Cabinets
Model Number
Type
Protection
Quantity x Voltage x Ah
Dimensions, W x D x H,
mm
Shipping dimensions, W
x D x H, mm
Unit weights, kg
Dimensions, W x D x H,
mm
Environment
Operating temperature
Storage temperature
Relative Humidity
(Operation)
Operating Altitude
6 Specifications
EDGE-1500IRT2UXL
EDGE-2200IRT2UXL
1500VA / 1350W / 6.7 A
2200VA / 1980W / 9.8A
106% - alarm warning and shutdown after 60 seconds
126% - alarm warning and shutdown after 50 seconds
151% - alarm warning and shutdown after 2 seconds
201% - alarm warning and immediate shutdown
Electronic (over current, short circuit w/ latching shutdown)
98% or greater for 200/208/220/230/240 VAC
96% or greater for 200/208/220/230/240 VAC
EDGE-
1500IRT2UBATKIT
2200IRT2UBATKIT
Electronic (overcurrent, short circuit with latching shutdown)
Valve-regulated lead-acid (VRLA) in compliance with UL 1989
4 x 12V x 9Ah
GXT5-EBC48VRT2U
Valve-regulated lead-acid (VRLA) in compliance with UL 1989
4 x 12V x 9Ah
430 x 497 × 85
28.5
41.5
EDGE-3000IRT2UXL
101% - alarm warning
4 hours to recover 90%
EDGE-
EDGE-
3000IRT2UBATKIT
6 x 12V x 7Ah
GXT5-EBC72VRT2U
Circuit breaker
6 x 12V x 9Ah
430 x 602 x 85
570 x 617 x 262
0 °C to 40 °C
- 25 °C to +55 °C without battery inside
20% to 90%, non-condensing
3000 m @ 0°C to 40 °C without derating
Liebert® EDGE Installer/User Guide
EDGE-3000IRT3UXL
3000VA / 2700W / 13.3A
EDGE-
3000IRT3UBATKIT
6 x 12V x 10Ah
39
50
49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents