Vertiv Liebert EDGE Installer/User Manual page 32

Table of Contents

Advertisement

Liebert® EDGE Installer/User Guide
Settings based on backup time
Control outlets based on battery backup time remaining.
Threshold of turning off the outlet (min)
Turn on when power returns for (min)
Settings based on capacity
Control outlets based on battery capacity remaining.
Threshold of turning off the outlet (%)
Turn on when power returns for (min)
28
When the selected amount of time remains on battery mode, the outlet is turned off.
Select the checkbox to enable or disable (default) the option.
0 - 30 minutes (default of 5)
Length of time after the mains input power returns before turning on the outlet. Select
the checkbox to enable or disable (default) the option.
0 - 30 minutes (default of 0)
When the selected percentage of capacity remains in battery mode, the outlet turns off.
Select the checkbox to enable or disable (default) the option.
20 - 80 % (default of 20)
Length of time after the mains input power returns before turning on the outlet. Select
the checkbox to enable or disable (default) the option.
0 - 30 minutes (default of 0)
4 Operations