Table 6.1 Specifications, EDGE-500IRM1U,EDGE-1000IRM1U and EDGE-1500IRM1U (continued)
MODEL
Power Rating @ 230V
Output
Output Voltages (on battery)
Output Frequency (on battery)
Output Receptacles - not
controllable
Output Receptacles - controllable
Transfer Time
Output Waveform (on Battery)
Output Overload Operation
Protection
AC-mode Efficiency
Buck- Boost1- and Boost2- mode
Recharge Time
Internal Battery
Part Number
Protection
Type
Quantity x Voltage x Ah
Environment
Operating temperature
Storage temperature
Relative Humidity (Operation)
Operating Altitude
Audible Noise
Agency
44
EDGE-500IRM1U
500VA / 450W / 2.2A
200 / 208 / 220 / 230 / 240 VAC (230 VAC is factory default)
Adjustable with Input Waveform Sensitivity setting.
106% - alarm warning and shutdown after 60 seconds
126% - alarm warning and shutdown after 50 seconds
151% - alarm warning and shutdown after 2 seconds
201% - alarm warning and immediate shutdown
Electronic (over current, short circuit w/ latching shutdown)
98% or greater for 200/208/220/230/240 VAC
94% or greater for
200/208/220/230/240 VAC
EDGE-500I1UBATKIT
Electronic (overcurrent, short circuit with latching shutdown)
Valve-regulated lead-acid (VRLA) in compliance with UL 1989
2 x 6V x 9Ah
- 25 °C to +55 °C without battery inside
3000 m @ 0°C to 40 °C without derating
EDGE-1000IRM1U
1000VA / 900W / 4.4A
Autodetect 50/60 Hz ±1%
(3) IEC 320 C13
(3) IEC 320 C13
SeeSettings Submenu
Pure Sinewave
101% - alarm warning
96% or greater for 200/208/220/230/240 VAC
4 hours to recover 90%
EDGE-1000I1UBATKIT
4 x 6V x 9Ah
0 °C to 40 °C
20% to 90%, non-condensing
<45 dBA AVR mode, >70% load
<55 dBA Battery mode
EDGE-1500IRM1U
1500VA / 1350W / 6.7A
for details.
EDGE-1500I1UBATKIT
6 x 6V x 9Ah
6 Specifications