Liebert® EDGE Installer/User Guide
Input Parameter Options
Input Waveform sensitivity
Input waveform sensitivity setting.
Output Parameter Options
Voltage selection
Nominal voltage setting. Set the nominal system voltage to match the input voltage of the UPS
Frequency selection
Selects the frequency of the output:
Battery Parameter Options
External battery AH (2U and 3U VRLA models only)
Sets the amp-hour rating of the external battery. This setting should only be adjusted when
using third-party external batteries with the "External battery cabinets" setting set to 0. Amp-
hours are calculated automatically when using Vertiv EBCs by using the "External battery
cabinets" setting.
External battery cabinets (2U and 3U VRLA models only)
Sets the number of attached external battery cabinets or allows the number of EBCs to be
detected automatically with Autodetect. Autodetect is used only for Vertiv EBCs. If more than 6
Vertiv EBCs are connected, autodetect does not function and this must be set manually. For
third-party external batteries, set this option to 0 and use "External battery AH" setting above.
22
High (Default) (4 to 6 ms typical)
Medium (6 to 8 ms typical)
Low (8 to 10 ms typical)
200 V
208 V
220 V
230 V (default)
240 V
Auto : Automatically detects frequency of utility/mains power and sets the nominal
frequency to match (default)
50 Hz
60 Hz
0 - 118 Ah (default of 0)
0 - 6
Autotest (default)
4 Operations