Vertiv Liebert EDGE Installer/User Manual page 31

Table of Contents

Advertisement

Outlet1 Parameter Options
Turn on/off outlet (LI models)
Turns on or turns off the outlet based on the current state. Provides a confirmation window
with Yes/No options to confirm turning on the outlet.
Turn off outlet (VRLA models)
Opens the dialog to turn off the programmable outlet.
Reboot outlet (VRLA models)
Opens the dialog to turn on the programmable outlet.
Turn on delay
Length of time before outlet turns on after UPS start-up.
Turn off when UPS overload on battery
When this option is enabled, the programmable outlet will turn off if the UPS is overloaded while
in battery mode.
Settings based on discharge time
Controls outlets based on amount of time the battery has discharged.
Threshold of turning off the outlet (min)
Turn on when power returns for (min)
4 Operations
0 - 30 minutes (default of 0)
Enable
Disable (default)
Length of time that the outlet is powered after the batteries begin to discharge. Select
the checkbox to enable or disable (default) the option.
0 - 30 minutes (default of 5)
Length of time after the mains input power returns before turning on the outlet. Select
the checkbox to enable or disable (default) the option.
0 - 30 minutes (default of 0)
Liebert® EDGE Installer/User Guide
27