Installation

2.6 Digital Communicator

Two independent telephone lines can be connected to the control panel. Telephone line control/command is made possible via double
line seizure as well as usage of an RJ31X style interconnection. Note that it is critical that the panel's digital communicator be located as
the first device on the incoming telephone circuit to properly function.
Important! The DACT must not be used to dial a phone number that is call-forwarded.
Network
Service
Provider's
Facilities
Telephone
Line
Network
Demarcation
Point
The control panel's digital communicator is built into the main circuit board. Connection and wiring of two phone lines is required as
shown below.
Primary
phone line
active LED
J8
30
RJ31X
Jack
FACP with DACT
Telephone
Answering
System
Figure 2.12 DACT Installation
Secondary
phone line
active LED
J9
Modular female
connectors
Male plug
connectors
Figure 2.13 Wiring Phone Jacks
Customer Premises Equipment and Wiring
Unused
RJ-11 Jack
Fax Machine
Telephone
(Secondary Lines)
Incoming Telco
phone lines
Green Wire
Tip
to premise phones
Red Wire
Ring
1 2 3 4 5 6
7
8
RJ31X
Jack
Note: Shorting bars
inside RJ31X Jack
Secondary
removed during
phone line PH-2
male plug insertion
(ordered separately)
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C6 6/12/2018
Digital Communicator
Computer
Telephone
Unused
J-11 Jack
(Primary Lines)
Incoming Telco
Tip Green Wire
phone lines
Red Wire
Ring
Ring
Tip
1 2 3 4 5 6 7
8
RJ31X
Jack
7 foot cable
MCBL-7
Ring
to premise phones
Tip
Primary
phone line
PH-1