Specifications
Alarm Silence
System Reset/Lamp Test
Drill
•
LED Indicators
Fire Alarm
Supervisory
Trouble
AC Power
Alarm Silence
Primary and Secondary Phone Line Active LEDs
•
Piezo sounder for alarm, trouble and supervisory
•
24 volt operation
•
Low AC voltage sense
•
Alarm Verification
•
NACs Programmable for:
Silence Inhibit
Auto-Silence
Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)
Selective Silence (horn-strobe mute)
Temporal or Steady Signal
Silenceable or Nonsilenceable
•
Automatic battery charger with charger supervision
•
Silent or audible walktest capabilities
•
Optional PS-Tools utilityfor local or remote Upload/Download of program and data
•
Optional N-CAC-5X Class A Converter Module for NACs and IDCs
•
Optional 4XTM Transmitter Module
•
Optional ANN-SEC card for a secondary ANN-BUS
1.2 Specifications
NOTE: For wiring specifications, refer to"Wire Requirements" on page 125.
AC Power
SFP-5UD (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps
SFP-5UDC (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps
SFP-10UD(C) (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps
SFP-5UDE (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps
SFP-10UDE (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps
Wire size: minimum #14 AWG (2.0 mm
Supervised, nonpower-limited
Battery (sealed lead acid only) - J12
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp
Supervised, nonpower-limited
Maximum Charger Capacity: 18 Amp Hour battery for SFP-5UD, and 26 Amp Hour battery for SFP-5UDC and SFP-10UD(C)/E [two
18 Amp Hour batteries can be housed in FACP cabinet. Larger batteries require a separate battery box such as the NFS-LBB or BB-26
and the CHG-75 or CHG-120 Battery Charger.]
Minimum Battery Size: 7 Amp Hour (12 Amp Hour for SFP-5UD-7C & SFP-10UD-7C)
Initiating Device Circuits - TB4 (and TB6 on SFP-10UD only)
Alarm Zones 1 - 5 on TB 4 (SFP-5UD and SFP-10UD)
Alarm Zones 6 - 10 on TB6 (SFP-10UD only)
Supervised and power-limited circuitry
Operation: All zones Style B (Class B)
Normal Operating Voltage: Nominal 20 VDC
Alarm Current: 15 mA minimum
Short Circuit Current: 40 mA max.
Maximum Loop Resistance: 100 ohms (700 ohms per zone for linear heat detection - See Section 2.3, "Input Circuits" for more informa-
tion.)
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)
Standby Current: 2 mA
Refer to the Notifier Device Compatibility Document for listed compatible devices
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C6 6/12/2018
2
) with 600V insulation