Honeywell NOTIFIER SFP-5UD Series Manual page 15

Fire alarm control panels
Hide thumbs Also See for NOTIFIER SFP-5UD Series:
Table of Contents

Advertisement

Specifications
The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available
from the FACP with the FLPS-3 power supply. This applies to the SFP-5UD and SFP-5UDE.
Special Application
Nonresettable or
Resettable Power
Special Application
Resettable Power
ANN-BUS
ANN-SEC
Option Card
Synchronization
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C6 6/12/2018
TB9
0.5 amp max
per circuit
0.5 amp max
per circuit
TB5
2.5 amps max
NAC #1
per circuit
NAC #2
2.5 amps max
per circuit
TB7
2.5 amps max
NAC #3
per circuit
NAC #4
2.5 amps max
per circuit
TB3
Primary
0.5 amp max
per circuit
TB1
0.5 amp max
per circuit
TB2
Remote
0.040 amp max
per circuit
Output
Refer to the battery calculations section for additional information.
Figure 1.1 Current Availability with FACP and FLPS-3 Power Supply
Standby
1.0 amp max
per panel
Standby
1.0 amp max
per panel
Product Description
Alarm
3.0 amps max
per panel
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier sfp-10ud seriesNotifier sfp-5udNotifier sfp-5udeNotifier sfp-5udcNotifier sfp-10udNotifier sfp-10ude ... Show all

Table of Contents