Honeywell NOTIFIER SFP-5UD Series Manual page 61

Fire alarm control panels
Hide thumbs Also See for NOTIFIER SFP-5UD Series:
Table of Contents

Advertisement

Master Programming Level
ACC Message
Pressing 2 for ACC MSG # while viewing Edit Input Zone Screen #4 will cause the following screens to be displayed:
ACC MSG NUMBER
1=NO MSG-ACTIVE
2=NO MSG-INACTIVE
3=MESSAGE 1
ACC Message Screen #1
Using these screens, the programmer can assign an audio message to each input zone. The NO MSG-ACTIVE option is the factory
default selection which means that no message has been programmed for the input zone but its corresponding NFV-25/50ZST audio
zone will turn on when this input zone goes active (if an input zone with a programmed audio message goes active, the message will also
be played over this zone). The NO MSG-INACTIVE option will not turn on the corresponding NFV-25/50ZST audio zone when this
input goes active. If MESSAGE 1 through 5 is the programmed option, the selected message will play when the FACP is connected to an
NFV-25/50ZST Audio Panel via the ANN-BUS and the corresponding FACP input zone goes into alarm.
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C6 6/12/2018
ACC MSG NUMBER
1=MESSAGE 2
2=MESSAGE 3
3=MESSAGE 4
ACC Message Screen #2
ACC MSG NUMBER
1=MESSAGE 5
ACC Message Screen #3
Programming
61