Programming
Ademco Contact ID Format - Secondary Central Station Phone Number
The information shown in Table 3.5 is automatically programmed for the Secondary Central Station phone number Event Codes when
Ademco Contact ID Format is selected. To disable event reporting, select the desired Event Code to be disabled and press 0 or Clear and
then Enter to disable it. (Enter must be pressed to save the selection. Pressing Escape will not save the selection).
86
Event Description
Secondary # Zone 1 - 10 Alarm
Secondary # Zone 1 - 10 Disabled
Secondary # Drill
Secondary # AC Fault
Secondary # Zone 1 - 10 Fault
Secondary # Zone 1 - 10 Dirty
Secondary # Earth Fault
Secondary # Low Battery Fault
Secondary # No Battery Fault
Secondary # Telco Primary Line Fault
Secondary # Telco Secondary Line Fault
Secondary # NAC #1 Fault
Secondary # NAC #2 Fault
Secondary # NAC #3 Fault
Secondary # NAC #4 Fault
Secondary # NAC #1 Disable
Secondary # NAC #2 Disable
Secondary # NAC #3 Disable
Secondary # NAC #4 Disable
Secondary # Charger Fault
Secondary # Comm Trouble Primary #
Secondary # Comm Trouble Secondary #
Secondary # Printer Fault
Secondary # ANN-BUS Fault
Secondary # Option Card Fault
Secondary # CS CALC Fault
Secondary # System Off Normal
Secondary # System Test Message
Secondary # System Abnormal Test Message
Secondary # Upload/Download Request
Secondary # Upload Successful
Secondary # Download Successful
Secondary # Upload/Download Failed
Secondary # Voice EVAC Fault
Secondary # Power Supply Sync fault
Table 3.5 Ademco Contact ID Secondary # Event Codes
Event Code Settings
Active
115
570
604
301
380
380
310
302
311
351
352
321
322
326
327
521
522
526
527
300
354
354
336
330
333
304
308
602
608
411
416
412
413
330
300
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C6 6/12/2018