Master Programming Level
Type
To select the type of zone being programmed, press the 2 key while viewing the Edit Input Zone Screen #2. This will cause the control
panel to display the following Zone Type Screen:
Pressing the down arrow key will display additional zone types as indicated in the following table.
Some of the following Zone Types are not available for Canadian applications. Refer to "Canadian Option" on page 70 for additional
details.
Zone Type
Pull-Station
Waterflow
Waterflow Nonsilenceable
Combo
Combo AutoResettable
2-Wire Detector
Normally Open Contact
Fire
Tamper
Supervisory
Supervisory AutoResettable
Medic-Alert
Hazard-Alert
Tornado-Alert
Proc-Mon
Procmon-AR
AC-Loss-Mon
Ack-Switch
Sil-Switch
Drill-Switch
Reset-Switch
PAS-Bypass
Drill-Switch AutoResettable
While viewing any Zone Type screen, select the type of zone being programmed by pressing the corresponding keyboard number key.
The display will return to Edit Input Zone Screen #2 and indicate the selection next to the Type option.
NOTE: Almost any Input Zone type can activate an NFV-25/50ZST audio zone and output an assigned message with the exception of
ACKNOWLEDGE, SILENCE, RESET and PAS BYPASS Switches. The DRILL Switch (or input programmed as a drill switch) will cause all
of the corresponding NFV-25/50ZST audio zones to go active and will output Message 1.
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C6 6/12/2018
ZONE TYPE
1=PULL STATION
2=WATERFLOW
3=WATERFLOW NS
Zone Type Screen #1
Action When Activated
Fire Alarm
Fire Alarm Delayed (uses waterflow delay)
Fire Alarm (uses waterflow delay)
Fire/Supervisory (uses waterflow delay)
Fire/Supervisory AR, nonlatching (uses waterflow delay)
Fire Alarm
Fire Alarm
Fire Alarm
Supervisory
Supervisory, latching
Supervisory, nonlatching
Supervisory, latching
Supervisory, latching
Supervisory, latching
Piezo
Piezo, nonlatching
Trouble
Acts like panel Acknowledge Key
Acts like panel Alarm Silence Key
Acts like panel Drill Key
Acts like panel Reset Key
Positive Alarm Sequence Disable
Acts like panel Drill Key, nonlatching
Table 3.1 Zone Types