ANN-BUS Devices
provide these buttons. Communication between the N-ANN-80(C) and FACP is accomplished over a two wire serial interface employ-
ing the ANN-BUS communication format. The devices are powered, via two additional wires, from either the host FACP or remote UL-
listed, filtered, power supply.

Specifications

Operating Voltage Range: 18 VDC to 28 VDC
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
 Normal/Standby (no activity): 37.0 mA
 Trouble: 39.0 mA
 Alarm: 40.0 mA
 AC Fail ( not backlit): 15.0 mA
For use indoors in a dry location

Installation

Ensure that all power (AC and DC) has been removed from the FACP before installing the annunciator.

Opening/Closing Annunciator

The following procedure details the steps used to open the annunciator in order to access the terminal block and DIP switches (refer to
figure below):
1.
Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise
2.
Push in the snap latch located on the right side of the unit while pulling the cover open
3.
To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the cover closed, snapping it shut
4.
Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key

Mounting

The N-ANN-80 can be surface or semi-flush mounted to a single, double or 4" square electrical box. Select and remove the appropriate
knockout(s), pull the necessary wires through the knockouts and mount the annunciator in or on the wall depending on the type of instal-
lation desired.
The ANN-SB80KIT(-R/-B/-W) is an available mounting kit for the ANN-80 annunciator. The kit comes with a surface backbox and sur-
face wedge for angled viewing. The two pieces can be used separately or can be stacked together.
The N-ANN-80 cover must be attached to the annunciator backplate before mounting the annunciator to the electrical box/wall. The
cover cannot be reattached or removed after the annunciator has been mounted.
Annunciator mounted on
surface wedge from the
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C6 6/12/2018
Annunciator cover
with LCD display
Key switch shown
in ON position
ANN-SB80KIT
Annunciator mounted on
surface backbox from the
ANN-SB80KIT
Annunciator backplate
Press in latch
and
Pull annunciator
cover open
Annunciator mounted on
stacked surface wedge
and backbox from the
ANN-SB80KIT
Installation
39