Figure 7 - Communication Cable - Grounding The Shield - Keyscan CA250 Series Technical Manual

Hide thumbs Also See for CA250 Series:
Table of Contents

Advertisement

Grounding Communication Cable Shield
When terminating the communication cable in the metal enclosure, ensure that the shield is insulated and
connected to the ground lug. Keyscan suggests Alpha PVC 10516 - #16 clear tubing or a comparable tubing to
insulate the shield. Do not connect the shield to GND on a communication terminal block.
Ground Lugs
The metal enclosure includes 1 ground lug pre-mounted near the top and 1 spare ground lug, which can be
mounted to one of the available ground lug studs. You can re-locate the ground lug inside the metal enclosure
to minimize the length of shield used.
Note
Keep all shield wires and cables away from the control board.
Cut View
KI-00110E-07-11
Keyscan Technical Guide (PC109x - 04.12)
Figure 7 – Communication Cable – Grounding the Shield
Metal Enclosure
Communication Cable
(RS-232)
Ground Lug
PC109x
Shield*
Alternate Ground Lug
Lug Stud
Illustration shows CB-485 using RS-232
communication as an example only.
Refer to the Communication section for
specific communication and ribbon
cable connections.
Communication Board
(CB-485)
*Insulate shield with PVC
tubing such as Alpha # 16
or comparable insulator
and connect to ground lug.
Knockout
Ground
Ground
Lug Stud
21