Figure 96 - Keyscan K-Kpr Sm - Keyscan CA250 Series Technical Manual

Hide thumbs Also See for CA250 Series:
Table of Contents

Advertisement

K-KPR Smart Versions
K-KPR-SM Mifare
K-KPR-SM/125
K-KPR-GOV
K-KPR-G/125
Diagram applies to
PC109x or newer
control board.
Yellow
(Not used by
Keyscan.) Isolate
and tape back.
Blue used for pre-alert
otherwise isolate and tape
back.
If connecting external
sound device, see Pre-Alert
Relay Option or refer to
ACU cut sheet enclosed
with panel for ACU/OCB8
relay assignments.
Shield not connected.
Isolate with electrical tape.
ACU
Ground
Lug
KI-00418E-11-11
Keyscan Technical Guide (PC109x - 04.12)

Figure 96 - Keyscan K-KPR SM

1
2
3
4
5
6
7
8
9
0
#
Yellow
Shield
C1
LED D1
D0
PWR
(BEEP)
WHT
GRN
RED
Reader terminal on control board
Optional Wiring
Purple (Read Mode)
- when not connected, read mode set for secure
sector read only. Isolate and tape back. (This is
the recommended mode which offers higher
security.)
– when connected, read mode set for secure
sector or CSN. If secure sector unrecognized,
subsequently reads the CSN sector of card.
Connect to GND Black wire at reader.
Orange (Tamper)
- when using an optional Tamper Switch (Normally
Closed) locally at reader, connect to GND Black
wire.
- when not using Tamper Switch connect to GND
Black wire at reader.
Shield not connected.
Isolate with electrical tape.
Purple
Orange
6 conductors – shielded 22 AWG
Maximum 500 ft (152.4 m)
May require 2 additional conductors
if using external pre-alert device.
GND
BLK