Figure 34 - Terminate Floor Input Wiring Ec2500B - Keyscan CA250 Series Technical Manual

Hide thumbs Also See for CA250 Series:
Table of Contents

Advertisement

Cut View of EC2500B
Elevator A - 16 Floor Status Inputs
Floors 1 - 8
Door Inputs - A
1
2
3
4
5
Elevator A
Call Button Status
Normally Open
Dry Contact
Relay
Floor monitoring inputs (separate dry contacts) provided by 3
KI-00137E-07-11
Terminate Reader Wiring at ACU
For reader cable, use six (6) conductors 22 AWG shielded (6 conductors 18 AWG shielded for elevators) or a
cable with overall shielding. Use 18 AWG for current demanding readers such as the Indala PX620 or the
HID5375. The shielding wire must be connected to the earth ground lug at the ACU, isolated and taped at the
reader. The maximum reader distance is 500 feet (152.4 m) from the ACU when transmitting a Wiegand signal.
If the distance is greater than 500 feet (152.4 m), install one WIEEX2 per reader, which extends the distance
to 4000 feet (1219.2 m). See Appendix F –WIEEX2 & CWIEEX2 on page 154.
Reader Wiring
Red – Positive DC Power. For readers that draw more current, connect the red wire directly to the power
supply.
Black – Ground (GND)
Brown – Light Emitting Diode (LED) on reader
Green – Data output bit 0
White – Data output bit 1
Blue – optional pre-alert (reader beeper)
For specific reader wiring review the appendices listed in the Table of Contents.
Keyscan Technical Guide (PC109x - 04.12)
Figure 34 – Terminate Floor Input Wiring EC2500B
Floors 9 - 16
Common
RTE Inputs - B
6
7
8
1
2
3
4
5
6
7
8
Elevator A
Call Button Status
1 of 16
12 of 16
Normally Open
Dry Contact
N.O.
Relay
Elevator B - 16 Floor Status Inputs
Floors 1 - 8
Common
AUX Inputs - C
Common
1
2
3
4
5
6
7
8
Elevator B
Call Button Status
Normally Open
Dry Contact
N.O.
Relay
rd
party elevator company.
Floors 9 - 16
AUX Inputs - D
Common
9
10
11
12
13
14
15
16
7 of 16
N.O.
48