NETCOM6P/ACU RN (Encrypted) Installation
Guide
Enclosed with the NETCOM6P are two sets of instructions for reverse network (RN)
communication:
For mounting a NETCOM6P directly on the ACU control board with reverse network
communication, follow the instructions contained in this installation guide
For mounting a NETCOM6P on a CIM circuit board with reverse network
communication, follow the NETCOM6P/CIM RN (Encrypted) Installation Guide also
enclosed with the NETCOM6P
If you require NETCOM6P instructions for a non-reverse network application, refer to the
Keyscan Product Documentation Library CD.
The NETCOM6P is only compatible with CIM modules or plugged directly into a PC109x or
higher control board's M1 socket for reverse network communication.
Before commencing to install the NETCOM6P, be sure to review the Reverse Network
Overview.
Reverse Network Overview
Keyscan's RN licenses—AUR-RN for Aurora, K-RN for System VII and V-RN for Vantage—
are designed so that a programmed access control unit at a remote location initiates
communication via an encrypted NETCOM6P over a private or public network to the
PC/server at a host location.
Installation Coordination – Host & Remote Locations
The RN license involves installing and configuring reverse network encrypted
communication software at a host location and installing hardware components at a remote
location. You must coordinate certain settings between the two locations in order that the
ACU/NETCOM6P at the remote location can establish network communication back to the
PC/server with the encrypted communication software at the host location.
the technician installing the hardware components must have a host-location IP
address that the ACU connects to on the network
both the host and remote locations must have the same encryption key
the host location requires the serial # of the designated reverse network control
board
a valid path and connectivity must exist from the PC/server with the encrypted
reverse network communication manager at the host location to the
NETCOM6P/reverse network control board at the remote location—may require a
network administrator
The hardware technician must program the access
control board with a host-location IP address along with
other settings. The IP address the technician programs
into the control board depends on the network
configuration. We have provided two general network
configuration outlines: an Internet/Intranet/WAN
configured network that is exposed publicly and a LAN
that is closed. Refer to the network configuration that
best approximates your network application.

Advertisement

loading
Need help?

Need help?

Do you have a question about the NETCOM6P and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Keyscan NETCOM6P

  • Page 1 If you require NETCOM6P instructions for a non-reverse network application, refer to the Keyscan Product Documentation Library CD. The NETCOM6P is only compatible with CIM modules or plugged directly into a PC109x or higher control board’s M1 socket for reverse network communication.
  • Page 2 Encryption Key: 12345678 - Port: 3001 12345678 12345678 12345678 (May also include an alternate host router external IP address if available) Common AUX Inputs - D Common AUX Inputs - E KI-00453E-08-12 Keyscan Inc. A Member of the Kaba Group...
  • Page 3 AUX Inputs - D Common AUX Inputs - E Encrypted NETCOM6P Control Board Internal Static IP: 192.168.0.4 Reverse Network Programming: Encryption Key: 12345678 - PC/Server internal IP: 12345678 12345678 12345678 192.168.0.2 RN Port: 3001 KI-00454E-05-12 NETCOM6P/ACU RN (Encrypted) Installation Guide...
  • Page 4: Parts List

     Ensure you install the latest Keyscan NETCOM Program Tool utility on the enclosed CD on a laptop or PC that can be serially connected to program the NETCOM6P Important The NETCOM6P involves 2 connection procedures, temporary serial programming connections and permanent operation connections.
  • Page 5 1 2 3 4 5 6 7 8 Protective ACU System Configuration Cover Jumpers J16 Location of J16 is the ABCDEFGH same on all CA & EC control boards. COMMUNICATION STATUS TD1 RD1 TD2 RD2 TD3 RD3 TD4 RD4 KI-00143E-07-11 NETCOM6P/ACU RN (Encrypted) Installation Guide...
  • Page 6 CD-ROM drive. The utility auto-starts. Follow the on-screen prompts. About the Encryption Key The encryption key for the NETCOM6P must consist of one of the following bit settings: 32 characters (128 bit), 48 characters (192 bit) or 64 characters (256 bit). Characters can be as follows in any combination: ...
  • Page 7 Steps to Program and Install a NETCOM6P The NETCOM6P plugs directly into a PC109x or higher control board. Please note that this configuration only supports a single panel communication bus. To program the NETCOM6P, use a direct serial connection via the RS-232 (COM4) terminal block on the ACU control board as instructed.
  • Page 8 Steps to Install and Program the NETCOM6P…cont’d On the control board, set communication for M1 to program mode for the NETCOM6P depending on the version of PC109x control board:  J16 – pins F and G - ON  S2 DIP Switches – 7 and 8 - ON Connect the serial programming cable from the RS-232 (COM4) terminal on the control board to the laptop or PC as illustrated in Figure 5.
  • Page 9 12. From the Program NETCOM6B, NETCOM6 & NETCOM6P screen, enter the IP address assigned to the NETCOM6P. If using DHCP, enter 0.0.0.0 in the IP Address to Assign. 13. If a Subnet Mask is required, select it from the drop down list.
  • Page 10 For additional programming tips, press the F1 key with the Keyscan NETCOM Program Settings screen open. 29. After the NETCOM6P has been programmed, momentarily place a jumper ON J6 Reset or press and release the S1 switch on the control board.
  • Page 11 S2 DIP Switches – Turn S2 – switches 7 and 8 OFF. And then press and release the S1 switch. Return to the PC/laptop with the NETCOM Program Tool Utility. From the Keyscan NETCOM Utility screen, select the Keyscan Hyper Terminal button.
  • Page 12 To set a port number which is an override to the Reverse Network Port Number programmed into the NETCOM6P, select 5) Set Port Number and enter a valid port. This override port can also be entered in the Keyscan Client software.
  • Page 13 Steps to Program the Control Board with a Host-Location IP Address Cont’d 21. Re-mount the ACU protective cover. 22. Plug the Ethernet cable into the NETCOM6P for on-going permanent operation. See figure 5. 23. Re-apply power after the ACU protective cover has been re-mounted.
  • Page 14 Figure 5 illustrates serial programming connections from the PC or laptop to the NETCOM6P via M1 on the control board using the enclosed data cables. If the PC or laptop does not have a serial port, use Keyscan's optional USB-SER adaptor. Figure 5 - Serial Programming Connections...
  • Page 15 Figure 6 - Serial Programming Connections with USB-SER Adaptor PC or laptop with Keyscan NETCOM Program Tool Utility. For programming a NETCOM2P or NETCOM6P TAMPER TB3 SWITCH J16 – jumpers F & G - ON 485 OUT 485 IN S2 – DIP switches 7 & 8 - ON...
  • Page 16 NETCOM6P/Control Board Operational Connection Figure 7 illustrates NETCOM6P operating connections and jumper settings when mounted on a PC109x or higher control board. This configuration only supports a single control board communication bus. Figure 7 - NETCOM6P/PC109x (or higher) ACU Control Board...
  • Page 17 You may require the services of a network administrator to resolve network issues and ensure the PC/server with the encrypted reverse network communication manager at the host location has a valid path and connectivity to the NETCOM6P/control board at the remote location.
  • Page 18: Specifications

    Specifications Input Power Requirements Powered through control board (NETCOM6P 140 mA + control board 130 mA = 270 mA Network RJ45 (10/100 Base-T) Ethernet LAN/ WAN (TCP/IP protocol—port 3001) Agency Approvals—Ethernet Socket Complies with Class B limits of EN 55022: 1998 Direct & Indirect ESD.
  • Page 19 This page is intentionally blank. NETCOM6P/ACU RN (Encrypted) Installation Guide...
  • Page 20: Address Settings

    901 Burns St., E. Whitby, Ontario, Canada L1N 0E6 1.888.539.7226 (toll free Canada/USA) 905.430.7226 (elsewhere) www.keyscan.ca Technical Support Hours – 9:00 A.M. to 6:30 P.M. Eastern Time NETCOM6P/ACU RN Installation Guide (PC109x – 07.15) Keyscan Inc. A Member of the Kaba Group...