Menu and
register chart
16
MAIN MENU
STEP 0.5 s
Normal status, display off
Current on phase L1
Current on phase L2
Current on phase L3
Neutral current Io
Actual start value I>
Actual operate time t> or
multiplier k for stage I>
Actual start value I>>
Actual operate time t>>
of stage I>>
R
E
V.
Actual start value Io>
S
T
E
Actual operate time to>
P
or multiplier ko
.5
s
Actual start value Io>>
M
A
I
N
Actual operate time to>>
M
Actual setting of functional
E
switchgroup SGF1
N
U
Actual setting of blocking
switchgroup SGB
F
W
D.
Actual setting of relay
switchgroup SGR1
S
T
E
Latest memorized, event (n)
P
1
value of phase L1
1
s
Latest memorized, event (n)
2
value of phase L2
Latest memorized, event (n)
3
value of phase L3
Maximum demand current
4
value for 15 minutes
Duration of event (n)
5
starting of stage I>
Duration of event (n)
6
starting of stage I>>
Latest memorized, event (n)
7
value of neutral current Io
Duration of event (n)
8
starting of stage Io>
Duration of event (n)
9
starting of stage Io>>
Status of external relay
0
blocking / control signal
Relay unit identification
A
address for communication
SUBMENUS
PROGRAM 1 s
REV. STEP 0.5 s
SUBMENUS
Main setting
1
value for I>
Main setting
1
value for t> or k
Main setting
1
value for I>>
Main setting
1
value for t>>
Main setting
1
value for Io>
Main setting
1
value for to> or ko
Main setting
1
value for Io>>
Main setting
1
value for to>>
Main setting of
1
SGF1 checksum
Main setting of
1
SGB checksum
1 Main setting of
SGR1 checksum
Event (n-1)
1
value of phase L1
Event (n-1)
1
value of phase L2
Event (n-1)
1
value of phase L3
Highest maximum
1
demand value found
Duration of event (n-1)
1
starting of stage I>
Duration of event (n-1)
1
starting of stage I>>
Event (n-1)
1
value of current Io
Duration of event (n-1)
1
starting of stage Io>
Duration of event (n-1)
1
starting of stage Io>>
I>
I>&t>
I»&t»
0
000
Communication rate
1
setting [Bd]
FWD. STEP 1 s
Second setting
2
value for I>
Second setting
2
value for t> or k
Second setting
2
value for I>>
Second setting
2
value for t>>
Second setting
2
value for Io>
Second setting
2
value for to> or ko
Second setting
2
value for Io>>
Second setting
2
value for to>>
Main setting of
2
SGF2 checksum
Second setting of
2
SGB checksum
Main setting of
2
SGR2 checksum
Event (n-2)
2
value of phase L1
Event (n-2)
2
value of phase L2
Event (n-2)
2
value of phase L3
Duration of event (n-2)
2
starting of stage I>
Duration of event (n-2)
2
starting of stage I>>
Event (n-2)
2
value of current Io
Duration of event (n-2)
2
starting of stage Io>
Duration of event (n-2)
2
starting of stage Io>>
Io>
Io>&to>
Io»
Io»&to»
Loss of bus traffic time
2
counter 0..255 s
1
2
3
5
6
7
8
9
A

Advertisement