8
i)
Set the digit with the STEP push button.
j)
Press the PROGRAM push button to make the
decimal point flash.
k)
If needed, move the decimal point with the
STEP push button.
l)
Press the PROGRAM push button to make the
whole display flash. In this position, corre-
sponding to position c) above, one can see the
new value before it is recorded. If the value
needs changing, use the PROGRAM push but-
ton to alter the value.
m)
When the new value has been corrected, record
it in the memory of the relay module by pressing
the PROGRAM and STEP push buttons simul-
taneously. At the moment the information en-
ters the memory, the green dashes flash once in
the display, i.e. 1 - - -.
n)
Recording of the new value automatically initi-
ates a return from the setting mode to the
normal submenu. Without recording one can
leave the setting mode any time by pressing the
PROGRAM push button for about five sec-
onds, until the green display digits stop flashing.
o)
If the second setting is to be altered, enter
submenu position 2 of the setting I> by pressing
the STEP push button for approx. one second.
The flashing position indicator 1 will then be
replaced by a flashing number 2 which indicates
that the setting shown on the display is the
second setting for I>.
Enter the setting mode as in step c) and proceed
in the same way. After recording of the re-
quested values return to the main menu is
obtained by pressing the STEP push button
RESET
STEP
0 x
1 1. 0 5
PROGRAM
1 s
1 1. 0 5
RESET
STEP
0 x
1 1. 0 5
PROGRAM
1 s
1 1. 0 5
RESET
STEP
1 - - -
PROGRAM
PROGRAM
1 1. 0 5
5 s
RESET
STEP
2 1. 0 0
1 s
until the first digit is switched off. The LED still
shows that one is in the I> position and the
display shows the new setting value currently in
use by the relay module.