Measured Data - ABB SPAC 315 C User Manual And Technical Description

Feeder terminals
Table of Contents

Advertisement

Measured data

Switch
Function
number
SGR3/1 When SGR3/1 = 1, the start signal of the I> stage
is routed to TS1
SGR3/2 When SGR3/2 = 1, the trip signal of the I> stage
is routed to TS1
SGR3/3 When SGR3/3 = 1, the start signal of the I>> stage
is routed to TS1
SGR3/4 When SGR3/4 = 1, the trip signal of the I>> stage
is routed to TS1
SGR3/5 When SGR3/5 = 1, the start signal of the I
is routed to TS1
SGR3/6 When SGR3/6 = 1, the trip signal of the I
is routed to TS1
SGR3/7 When SGR3/7 = 1, the start signal of the I
is routed to TS1
SGR3/8 When SGR3/8 = 1, the trip signal of the I
is routed to TS1
Checksum for the factory settings of switchgroup SGR3
The measured current values are shown by the
three right-most digits of the display. The value
Indicator
Measured data
I
Line current on phase L1 as a multiple of the rated current I
L1
energizing input (0...63 x I
I
Line current on phase L2 as a multiple of the rated current I
L2
energizing input (0...63 x I
I
Line current on phase L3 as a multiple of the rated current I
L3
energizing input (0...63 x I
I
Residual current as a multiple of the rated current I
0
input (0...21 x I
0
0
displayed at the present time is indicated by a
LED indicator on the front panel.
).
n
).
n
).
n
).
n
Factory
setting
0
0
0
0
> stage
0
0
> stage
0
>> stage
0
0
>> stage
0
of the used
n
of the used
n
of the used
n
of the used energizing
n
Checksum
value
1
2
4
8
16
32
64
128
0
13