14
Terminal numbers:
Terminal Terminal Function
block
number
X0
1-2
1-3
4-5
4-6
7-8
7-9
25-26
25-27
61-62
63
65
66
96
97
85
86
98
99
X1
1-2-3
4-5
6-7
8-9
10-11
12-13
Phase current I
, 5 A
L1
Phase current I
, 1 A
L1
Phase current I
, 5 A
L2
Phase current I
, 1 A
L2
Phase current I
, 5 A
L3
Phase current I
, 1 A
L3
Neutral current I
, 5 A in SPAC 315 C and 1 A in SPAC 317 C
0
Neutral current I
, 1 A in SPAC 315 C and 0.2 A in SPAC 317 C
0
Auxiliary power supply. When dc supply voltage is used the posi-
tive pole is to be connected to terminal 61
Equipment earth terminal
OPEN output
Single-pole control: terminal 65 connects to CB OPEN coil
Double-pole control: terminal 65 connects to negative control
voltage pole
OPEN output
Double/Single-pole control: terminal 66 connects to positive
control voltage pole
OPEN output
Single-pole control: terminal 96 connects to terminal 97
Double-pole control: terminal 96 connects to CB OPEN coil
OPEN output
Single-pole control: terminal 97 connects to terminal 96
Double-pole control: terminal 97 connects to CB OPEN coil
CLOSE output
Single-pole control: terminal 85 connects to CB CLOSE coil
Double-pole control: terminal 85 connects to negative control
voltage pole
CLOSE output
Double/Single-pole control: terminal 86 connects to positive
control voltage pole
CLOSE output
Single-pole control: terminal 98 connects to terminal 99
Double-pole control: terminal 96 connects to CB CLOSE coil
CLOSE output
Single-pole control: term. 99 connects to terminal 98
Double-pole control: term. 99 connects to CB CLOSE coil
Self-supervision (IRF) signalling output. When auxiliary power is
connected and the device is operating properly the interval 2-3
is closed
Signal output 4. E.g.alarm from energizing current monitoring and
trip circuit supervision or 3I> alarm or 3I>> alarm or I
I
>> alarm, configured by user
0
Signal output 3, configured by user
Signal output 2, configured by user
Signal output 1, configured by user
Input CHANNEL 9
> alarm or
0