Appendix 2
Default
configuration
and interlocking 2
Default configuration and interlocking 2 is se-
lected by giving variable S100 the value 2. The
other parameters have the values given in the
chapter "Default values of the parameters".
Configuration
The configuration unit has three objects, a cir-
cuit breaker, a circuit breaker truck and an earth-
switch. The close state is indicated with red col-
our and the open state with green colour. The
following inputs, indicators and outputs are
used:
- Circuit breaker;
input channel 2, indicator 110, controlled by
outputs OPEN (20) and CLOSE (21)
- Circuit breaker truck;
input channel 1, indicator 109, not controlled
- Earth-switch;
input channel 3, indicator 116, not controlled
The configuration commands are as follows:
S109:1,1,1,0,11
S110:1,1,2,20,1
S116:1,0,3,0,0
Fig 18. Default confuguration 2.
Interlocking
The following rules apply for interlocking:
- The CB can always be opened.
- The CB can be closed if the CB truck is in
isolated position or if the CB truck is in the
service position and the earth-switch is open.
61
1
1
202
&
203
Fig. 19. Logic diagram for the default inter-
locking 2.
The interlocking program has the following
form:
M200:LOAD 61
M201:OUT 20
M202:LOAD 1
M203:AND 202
M204:AND 203
M205:OUT 21
M206:END
20
Enable CB opening
21
Enable CB oclosing