ABB SPAC 315 C User Manual And Technical Description page 92

Feeder terminals
Table of Contents

Advertisement

Output relay matrix
switchgroups SGR1,
SGR2 and SGR3
12
SGR1
The switches of switchgroup SGR1 are used to select the start and operate signals
to be routed to outputs SS1 and TS2.
SGR2
The switches of switchgroup SGR2 are used for routing the operate signals of the
protection stages to the outputs SS2 and SS3.
SGR3
The switches of switchgroup SGR3 are used to route the start and operate signals to
the start or auxiliary trip output TS1. Note! If the circuit breaker failure protection
has been taken in use with switch SGF1/4, it will also occupy the TS1 output.
Switch
Function
number
SGR1/1 When SGR1/1 = 1, the start signal of the I> stage is
routed to SS1
SGR1/2 When SGR1/2 = 1, the operate signal of the I> stage
is routed to TS2
SGR1/3 When SGR1/3 = 1, the start signal of the I>> stage is
routed to SS1
SGR1/4 When SGR1/4 = 1, the operate signal of the I>> stage
is routed to TS2
SGR1/5 When SGR1/5 = 1, the start signal of the I
is routed to SS1
SGR1/6 When SGR1/6 = 1, the operate signal of the I
is routed to TS2
SGR1/7 When SGR1/7 = 1, the staring signal of the I
is routed to SS1
SGR1/8 When SGR1/8 = 1, the operate signal of the I
is routed to TS2
Checksum for the factory settings of switchgroup SGR1
SGR2/1 When SGR2/1 = 1, the operate signal of the I> stage
is routed to SS2
SGR2/2 When SGR2/2 = 1, the operate signal of the I> stage
is routed to SS3
SGR2/3 When SGR2/3 = 1, the operate signal of the I>> stage
is routed to SS2
SGR2/4 When SGR2/4 = 1, the operate signal of the I>> stage
is routed to SS3
SGR2/5 When SGR2/5 = 1, the operate signal of the I
is routed to SS2
SGR2/6 When SGR2/6 = 1, the operate signal of the I
is routed to SS3
SGR2/7 When SGR2/7 = 1, the operate signal of the I
is routed to SS2
SGR2/8 When SGR2/8 = 1, the operate signal of the I
is routed to SS3
Checksum for the factory settings of switchgroup SGR2
Factory
setting
1
1
0
1
> stage
0
0
> stage
0
1
>> stage
0
0
>> stage
0
1
1
0
1
0
> stage
0
0
> stage
0
1
>> stage
0
0
>> stage
0
1
Checksum
value
1
2
4
8
16
32
64
128
171
1
2
4
8
16
32
64
128
165