The control module has the following event codes:
Channel
Code Event
0
E1
Key switch in position LOCAL
0
E2
Key switch in position REMOTE
0
E3
Output test switch SG1/1 ON
0
E4
Output test switch SG1/1 OFF
0
E5
Supervision functions disabled SG1/2 ON
0
E6
Supervision functions enabled SG1/2 OFF
0
E7
Trip circuit fault
0
E8
Trip circuit fault reset
0
E9
Energizing current input fault
0
E10
Energizing current input fault reset
0
1...3
E1
Change in status; xx -> 10 (open)
1...3
E2
Change in status; xx -> 01 (closed)
1...3
E3
Change in status; xx -> 11 (undefined)
1...3
E4
Change in status; xx -> 00 (undefined)
1...3
E5
OPEN output activated
1...3
E6
OPEN output reset
1...3
E7
CLOSE output activated
1...3
E8
CLOSE output reset
1...3
E9
Output activation inhibited 1)
1...3
E10
Failed to open or close 2)
1...3
E11
Attempt to activate an output without
open/close selection 3)
1...3
4...13
E1
Input channel activated
4...13
E2
Input channel reset
4...13
E3
SIGNAL1...4 output activated
4...13
E4
SIGNAL1...4 output reset
4...13
0
E50
Restarting
0
E51
Overflow of event register
0
E52
Temporary disturbance in data communication
0
E53
No response from the module over the data
communication
0
E54
The module responds again over the data
communication
0 not included in the event reporting
1 included in the event reporting
*
no code number
-
cannot be set
Weighting
Default
factor
value
1
1
2
1
4
0
8
0
16
0
32
0
64
1
128
0
256
1
512
0
V155 = 323
1
1
2
1
4
0
8
0
16
1
32
0
64
1
128
0
256
1
512
1
1024
1
V155 = 1875
1
1
2
1
4
0
8
0
V155 = 3
*
-
*
-
-
*
-
*
-