ABB SPAC 315 C User Manual And Technical Description page 55

Feeder terminals
Table of Contents

Advertisement

Data
kWh value per pulse
Energizing input and trip circuit
supervision function
Interlockings
Object indicator mode
Display indicator mode
Scaling of current measurement
Low limit for mA signal of active power
High limit for mA signal of active power
Low limit for mA signal of reactive power
High limit for mA signal of reactive power 0
Active power corresponding to the
mA signal at low limit
Active power corresponding to the
mA signal at high limit
Reactive power corresponding to the
mA signal at low limit
Reactive power corresponding to the
mA signal at high limit
Power measurement
Energy measurement
Configuration and interlocking
Channel Code
Data
direction
0
S3
RW(e)
0
S5
R
0
S6
R
0
S7
RW(e)
0
S8
RW(e)
0
S9
RW(e)
0
S12
RW(e)
0
S13
RW(e)
0
S14
RW(e)
S15
RW(e)
0
S16
RW(e)
0
S17
RW(e)
0
S18
RW(e)
0
S19
RW(e)
0
S91
RW(e)
0
S92
RW(e)
0
S100
RW(e)
Values
0.01...1000 kWh per pulse
0 = function enabled
(SG1/2=0)
1 = function disabled
(SG1/2=1)
0 = interlocking enabled
(SG1/1=0)
1 = interlocking disabled
(SG1/1=1)
0 = continuous display
(default setting)
1 = automatic switch-off
after 10 min.
(re-display from
∩ push-button)
2 = automatic switch-off
of CB and truck indi-
cators after 10 min.
if showing undefined
status, i.e. CB removed.
(re-display from
∩ push-button or
status change)
0 = continuous display
1 = automatic switch-off
after 5 min.
0.00...10000.00
-20...+20 mA
-20...+20 mA
-20...+20 mA
-20...+20 mA
- 999.99...+999.99
- 999.99...+999.99
- 999.99...+999.99
- 999.99...+999.99
0 = no power measurement
1 = power is measured
0 = no energy measurement
1 = energy is measured
0 = freely selectable
configuration and
interlocking program
1 = default 1
2 = default 2
10 = default 10
29

Advertisement

Table of Contents