ABB SPAC 315 C User Manual And Technical Description page 59

Feeder terminals
Table of Contents

Advertisement

Data
Activation of self-supervision output
Start display test
Internal fault code
Data communication address
Data transfer rate
Program version symbol
Type designation of the module
Reading of event register
Re-reading of event register
Reading of module status
information
Resetting of module status
information
Time reading and setting
R = Data which can be read from the module
W = Data which can be written to the module
(e) = Data which has to be stored in EEPROM (V151) after it has been changed
The data transfer codes L, B, C and T have been
reserved for event data transfer between the con-
trol module and the station level data commu-
nicator.
Channel Code
Data
direction
0
V165
W
0
V167
W
0
V169
R
0
V200
RW(e)
0
V201
RW(e)
0
V205
R
0
F
R
0
L
R
0
B
R
0
C
R
0
C
W
0
T
RW
The event register can be read by the L com-
mand only once. Should a fault occur e.g. in
the data transfer, it is possible, by using the B
command, to re-read the contents of the event
register. When required, the B command can
be repeated.
Values
0 = reset
1 = activate
1 = start display test
sequence;
overrides O.C.F. and/
or C.I.F. display
messages if active
Fault code
1...255
4800 Bd or 9600 Bd
E.g. 092 A
SPTO 1D6
Time, channel number
and event code
Time, channel number
and event code
0 = normal state
1 = module been subject
to automatic reset
2 = overflow of event
register
3 = events 1 and 2
together
0 = resetting
0.000...59.999 s
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Spac 317 c

Table of Contents