ABB SPAC 315 C User Manual And Technical Description page 42

Feeder terminals
Table of Contents

Advertisement

16
Example 3
To set a configuration similar to the default con-
figuration 1 (indicator 109 for circuit breaker
truck, indicator 110 for circuit breaker and in-
dicator 116 for an earthing switch), the follow-
ing commands are required:
>99WS198:0:XX
; Enter into setting mode
>99WS100:0:XX
; Enter into mode for free configuration
>99WS109:1,1,1,0,11:XX
; Circuit breaker truck : vertical red LEDs
indicate closed status for input channel 1.
No control
>99WS110:1,1,2,20,1:XX
; Circuit breaker : vertical red LEDs indi-
cate closed status for input channel 2.
Control outputs OPEN and CLOSE
>99WS116:1,0,3,0,0:XX
; Earthing switch : horizontal red LEDs in-
dicate closed status for input channel 3.
No control
>99WV151:1:XX
; Store the set parameters
After this the interlocking program has to be
written before it is possible to open or close the
circuit breaker. See Chapter "Interlocking".
Fig. 9. Object configuration set in example 3.
The selected configuration can be read indica-
tor by indicator or all together with one single
instruction.
Example 4
Reading the configurations of indicators 101...
116 by using one single instruction.
>99RS101/116:XX
This instruction will give the setting values of
each indicator (101 to 116 ), including those
not configured into the system. The parameter
values of the indicators not in use are zero.