Front Panel - ABB SPAC 315 C User Manual And Technical Description

Feeder terminals
Table of Contents

Advertisement

Front panel

Object status
indicators
8
Type designation and
rated values of the relay
fn=
package
Operation indicators;
output test and interlocked
operation
Indicators for input
channels 4...9
The pocket for channel
legend text film SYKU 997
Remote/Local key switch
Indicators for remote and
local mode
Indicator for auxiliary
U
power supply
Voltage range of power
supply and binary inputs
Fig. 4. Front panel of the control module SPTO 1D6 without the configuration plate SYKK _ and
the channel legend text foil SYKU 997.
The front panel includes 16 indicator units with
each four rectangular LED indicators, two green
and two red. The indicator units are used for
local status indication of the circuit breakers and
disconnectors of the switchgear cubicle. In the
control module SPTO 1D6 three of the 16 in-
dicator units can be utilized at a time. The indi-
cator units to be used are freely selectable by
the user, see chapter "Configuration".
A plastic configuration plate type SYKK_ with
a printed mimic diagram is inserted into a
pocket in front of the object indicator units. The
bottom of the pocket is open. By selecting a
proper configuration plate and by configuring
a new combination of indicator units different
object configurations of the switchgear cubicle
can be handled.
The configuration plate shows the combination
of circuit breakers and disconnectors of the
switchgear cubicle. The configuration plate fea-
tures transparent windows for the status indi-
cators that are in use. The status indicators not
in use are hidden.
One indicator unit consists of four LEDs, two
vertical and two horizontal. Two of the LEDs
are red and two are green. The red LEDs are
vertically and the green LEDs horizontally ar-
ranged in columns 1 and 3, see Fig. 5. In col-
umns 2 and 4 the green LEDs are vertically and
the red LEDs horizontally arranged. Due to this
SPAC 3_ _C
In = 1
/ 5 A ( I )
In = 0.2 / 1 A ( I o)
50
60 Hz
TEST
INTERLOCK
R
L
aux
80...265 V_
30...80 V_
RS 615
Object status indication matrix
The pocket for configuration
plate SYKK _
2
IRF
5
STEP
I
[kA]
L1
I
[kA]
L2
I
[kA]
L3
I
P [MW]
Q [MVar]
E [GWh,MWh,kWh]
O
SG1
1
2
0
1
RS 232
Serial No.
SPTO 1D6
Select
Close
I
and
Open
O
push-buttons
system both colours can be used to indicate ei-
ther the open or closed status of a switching
device.
Fig. 5. Example of a plastic configuration plate
SYKK __. The actual size of the configuration
plate is 72mm x 106.5 mm.
Simplified device
symbol
O<->I
Self-supervision
alarm indicator
Display for measured
values
Display step
push-button
Indicators for value
currently on display
Selector
Switchgroup SG1
RS 232 interface
Type designation
of the module

Advertisement

Table of Contents
loading

This manual is also suitable for:

Spac 317 c

Table of Contents