30
Data
Configuration of objects
(format; value 1, value 2, input No,
output code, value 3)
Selection of setting/run mode
Interlocking selection
Trip circuit supervision (TCS)
Supervision mode
Energizing current monitoring
Monitored phase currents
Operation delay for energizing
current monitoring alarm
Channel Code
Data
direction
0
S101
RW(e)
:
S116
0
S198
RW(e)
0
S199
RW(e)
0
S200
RW(e)
0
S201
RW(e)
0
S202
RW(e)
0
S203
RW(e) 1 = L1+L2+L3 (default)
0
S204
RW(e)
Values
- value 1;
0 = indicator not used
1 = indicator used
- value 2;
0 = vertical LEDs indicate
open status
1 = vertical LEDs indicate
closed status
- input number;
1...3 = input number 1...3
- output code;
0 = not controlled object
20 or 21 = outputs 20 or
21 used
- value 3;
0 = object other than CB
or CB truck
1 = object is a CB
11 = object is a CB truck
0 = program mode
1 = run mode
0 = no interlockings
1 = interlockings in use
0 = no TCS
1 = TCS in use
alarm via SIGNAL 4
2 = TCS in use, but
no contact alarm
0 = continuous supervision
1 = no TCS when TS2
activated (binary input
channel 13)
(default setting)
2 = no TCS when OPEN
signal activated
3 = no TCS when TS2
or OPEN signal
activated
0 = no monitoring
1 = monitoring in use
alarm via SIGNAL 4
2 = monitoring in use, but
no contact alarm
2 = L1+L2
3 = L1+L3
4 = L2+L3
3...60 s in 1 s steps
(default 15 s)