Quick reference
for setting
In the SPACOM system the event codes E52...
E54 are generated by the substation level con-
trol data communicator.
1) Event E9, output activation inhibited, is ob-
tained if the operation is inhibited by the in-
terlocking program or by an input channel
4...13.
If all the parameters are set at the same time,
the following instructions should be used when
changing between setting and run mode and
when storing the parameters.
The default values of the parameters related to
interlocking and configuration are:
S100 = 1
Default configuration and interlocking 1
S198 = 1
The interlocking program is in run mode
S199 = 1
Interlockings are in use
The following example shows the setting pro-
cedure.
Example 18
To select another configuration and interlock-
ing than default 1.
>99WS198:0:XX
; Change into setting mode
>99WS100:2:XX
; Select the default 2
>99WS198:1:XX
; Change into run mode
:
; Change other parameters
:
>99WV151:1:XX
; Store set parameters
2) Event E10, output activation fault, is given
if the status of the controlled object does not
change during the time of the output pulse.
3) Event E11, attempt to activate an output
without an open/close selection, is given
when a secured control is made in a situation
where the state of alert has not been defined.
Example 19
To select a user-specific configuration and in-
terlocking system.
>99WS198:0:XX
; Change into setting mode
>99WS100:0:XX
; Change into freely selectable mode
>99WS101:...
; Configuration commands
:
:
:
>99WM200:...
; Interlocking program
:
:
:
>99WS198:1:XX
; Change into run mode
:
; Change other parameters
:
>99WV151:1:XX
; Store set parameters
27