Download Print this page

Technical Data; Profibus Dp Interface - AUMA TIGRON TR-M30X Manual

Multi-turn actuators
Hide thumbs Also See for TIGRON TR-M30X:

Advertisement

Technical data

6.
Technical data
Information
6.1.

Profibus DP interface

Settings/programming the Profibus DP interface
Baud rate setting
Setting the fieldbus address
Configurable process representation
via GSD file
General Profibus DP interface data
Communication protocol
Network topology
Transmission medium
Profibus DP interface
Transmission rate/cable length
Device types
Number of devices
Fieldbus access
Supported Profibus DP functions
Profibus DP ident no.
36
The following tables include standard and optional features. For detailed information
on the customer-specific version, refer to the order-related data sheet. The technical
data sheet can be downloaded from the Internet in both German and English at ht-
tp://www.auma.com (please state the order number).
Automatic baud rate recognition
The Profibus DP address is set via the display of the device.
For an optimum adaptation to the process control system, the process representation input (feedback
signals) can be configured as desired.
Profibus DP according to IEC 61158 and IEC 61784
Line (fieldbus) structure. When using repeaters, tree structures can also be implemented. Coupling and
uncoupling of devices during operation without affecting other devices is possible.
Twisted, screened copper cable according to IEC 61158
EIA-485 (RS-485)
Baud rate (kbit/s)
9.6
93.75
187.5
500
1,500
DP master class 1, e.g. central controllers such as PLC, PC, ...
DP master class 2, e.g. programming/configuration tools
DP slave, e.g. devices with digital and/or analogue inputs/outputs such as actuators, sensors
32 devices without repeater, with repeater expandable to 126
Token-passing between masters and polling for slaves. Mono-master or multi-master systems are pos-
sible.
Cyclic data exchange, sync mode, freeze mode, fail safe mode
0x1144:
Standard applications with Profibus DP-V0 and DP-V1
Max. cable length
(segment length) without repeater
1,200 m
1,000 m
400 m
200 m
Multi-turn actuators
Profibus DP
Possible cable length with repeater
(total network cable length):
approx. 10 km
approx. 10 km
approx. 4 km
approx. 2 km

Advertisement