Siemens SIMATIC ET 200AL System Manual page 1514

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Number of connection resources of a station
Table 12- 1
Maximum number of connection resources supported for some CPU types
Connection resources of a
station
Maximum connection re-
sources of the station
of which reserved
of which dynamic
Connection resources of the
CPU
Max. additionally usable
connection resources by
plugging in CMs/CPs
Additional connection re-
sources CM 1542-1
Additional connection re-
sources CP 1543-1
Additional connection re-
sources CM 1542-5
Additional connection re-
sources CP 1542-5
The number of connection resources that a CPU or a communication module supports is
specified in the device manuals in the Technical Specifications.
Example
You have configured a CPU 1516-3 PN/DP with a CM 1542-1 communication module and a CP
1542-5 communication processor.
• Maximum connection resources of the station: 256
• Available connection resources:
– CPU 1516-3 PN/DP: 128
– CM 1542-1: 64
– CP 1542-5: 16
– Total: 208
The setup provides 208 connection resources. By adding further communication modules,
the station can support a maximum of 48 additional connection resources.
Communication
Function Manual, 05/2021, A5E03735815-AJ
1511
1512C
1511C
1513
96
128
86
118
64
88
32
40
12.1 Connection resources of a station
1515
1516
192
256
10
182
246
108
128
84
128
64
118
40
16
Connection resources
1517
1518
320
384
310
374
288
320
32
64
393

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents