Wilo Yonos GIGA-N 80 Installation And Operating Instructions Manual page 69

Table of Contents

Advertisement

Classification
No.
E030
E031
E032
Electronic
module error
E033
E035
E050
Communica-
tion errors
E051
E052
Installation and operating instructions Wilo-Yonos GIGA-N
Faults, causes and remedies
Fault
Cause
Excess elec-
Restricted air
tronic module
supply to heat
temperature
sink of elec-
tronic module
Hybrid/power
Ambient tem-
section excess
perature too
temperature
high
Intermediate
Voltage fluctu-
circuit under-
ations in the
voltage
mains
Intermediate
Voltage fluctu-
circuit over-
ations in the
voltage
mains
DP/MP: mul-
Multiple in-
tiple instances
stances of
of same iden-
same identity
tity
BMS commu-
Bus commu-
nication
nication inter-
timeout
rupted or timed
out, cable
breakage
Impermissible
Different
DP/MP com-
pumps
bination
DP/MP com-
MP communic-
munication
ation cable de-
time-out
fective
Remedy
Error type
Provide unob-
B
structed air ac-
cess
Improve room
B
ventilation
Check elec-
F
trical installa-
tion
Check elec-
F
trical installa-
tion
Reallocate
E
master and/or
slave (see
"Twin-head
pump installa-
tion/Y-pipe in-
stallation"
chapter)
Check cable
F
connection to
building auto-
mation
Contact cus-
F
tomer service
Check cable
E
and cable con-
nections
en
A
A
D
D
E
F
F
E
69