Wilo Yonos GIGA-N 80 Installation And Operating Instructions Manual page 52

Table of Contents

Advertisement

en
No.
Designation
Display orienta-
5.7.1.0
tion
Delivery head
correction
5.7.2.0
Switching fre-
quency
5.7.5.0
SBM function
5.7.6.0
Factory setting
5.7.7.0
Other settings 2
5.8.0.0
Pump kick
5.8.1.0
Pump kick act-
5.8.1.1
ive/inactive
Pump kick time
5.8.1.2
interval
Pump kick speed
5.8.1.3
Error acknow-
6.0.0.0
ledgement
Access disable
7.0.0.0
52
Operation
Type Symbol
Values/explanations
Display orientation
±
Display orientation
When delivery head correction is enabled,
±
the deviation from the differential pres-
sure measured by the factory-fitted
sensor on the pump flange is taken into
account and corrected.
Delivery head correction off
Delivery head correction on (factory set-
ting)
HIGH
High switching frequency (factory setting)
MID
Medium switching frequency
LOW
Low switching frequency
Settings for behaviour of signals
±
SBM run signal
SBM readiness signal
SBM mains on signal
OFF (default setting): settings are not
±
changed by confirming.
ON: confirming will reset the settings to
factory settings.
Caution! All manual settings will be lost.
ON (factory setting)
Pump kick is activated
OFF
Pump kick is deactivated
Can be set between 2 and 72 hours in 1-
±
hour steps
Can be set between the pump's minimum
±
and maximum speeds
For additional information, see "Acknow-
±
ledging errors" chapter.
Access disable feature inactive (changes
±
possible) (for additional information, see
"Activating/deactivating access disable"
chapter).
Display conditions
Only displayed in Δp-c mode. Not
displayed for all pump variants
Switchover/change must only be
carried out when the pump is at a
standstill (not when motor is run-
ning)
Not displayed when access disable
is active. Not displayed when BMS
is active.
Not displayed when access disable
is active. Not displayed when BMS
is active. For parameters that are
changed by a factory setting, see
"Factory settings" chapter.
Not displayed if pump kick is deac-
tivated
Not displayed if pump kick is deac-
tivated
Only displayed if an error is
present.