Operating Instructions - Wilo Yonos GIGA-N 80 Installation And Operating Instructions Manual

Table of Contents

Advertisement

Fig. 37: Error page (error status)
8.5.4
Menu groups
Basic menu
Info menu
Service menu
Error acknowledgement menu
Access disable menu
8.6

Operating instructions

8.6.1
Adjusting the setpoint
Installation and operating instructions Wilo-Yonos GIGA-N
Operation
E.025
ƒ
<1.0.0.0>: Setpoint settings
ƒ
<2.0.0.0>: Operating mode setting
ƒ
<3.0.0.0>: "Pump on/off" setting
The menus show settings that may need to be changed during normal operation of the
pump.
ƒ
<4.0.0.0>: Pump parameter display
The menu <4.0.0.0> and its sub-menu elements show measuring data, device data, op-
erating data and current statuses.
ƒ
<5.0.0.0>: Access to pump parameter settings
The menu <5.0.0.0> and its sub-menu elements provide access to basic system set-
tings for commissioning. The sub-elements are write-protected as long as service
mode is not activated.
CAUTION
Risk of material damage!
Incorrect changes to settings can lead to pump operation errors, which in turn can
lead to pump or system damage.
• Settings in service mode should only be made during commissioning and only by
qualified personnel.
ƒ
<6.0.0.0>: Error acknowledgement
If an error occurs, the display shows the error page. Pressing the operating button takes
you from the error page to the error acknowledgement menu. After a waiting period has
elapsed, pending fault messages can be acknowledged. For additional information, see
"Acknowledging errors" chapter.
CAUTION
Risk of material damage!
Acknowledging faults without eliminating their cause can cause further faults. Ma-
terial damage may occur to the pump or system.
• Only acknowledge errors after they have been rectified.
• Only allow qualified personnel to rectify faults.
• If in doubt, consult the manufacturer.
For additional information, see "Faults, causes and remedies" chapter
ƒ
<7.0.0.0>: Access disable
The "access disable" feature is available when DIP switch 2 is set to ON. The menu can-
not be reached via normal navigation.
Pressing the operating button activates or deactivates the access disable feature. The
selection is confirmed by pressing the operating button.