Wilo Yonos GIGA-N 80 Installation And Operating Instructions Manual page 51

Table of Contents

Advertisement

No.
Designation
LON/CAN/IF-
5.2.1.0
Module Wink/
Service
Local/remote
5.2.2.0
operation
Bus address
5.2.3.0
IF gateway val A
5.2.4.0
IF gateway val C
5.2.5.0
IF gateway val E
5.2.6.0
IF gateway val F
5.2.7.0
In1 (sensor in-
5.3.0.0
put)
In1 (sensor value
5.3.1.0
range)
In1 (value range)
5.3.2.0
In2
5.4.0.0
In2 active/inac-
5.4.1.0
tive
In2 (value range)
5.4.2.0
PID parameters
5.5.0.0
P parameter
5.5.1.0
I parameter
5.5.2.0
D parameter
5.5.3.0
Fault
5.6.0.0
HV/AC
5.6.1.0
Emergency op-
5.6.2.0
eration speed
Auto reset time
5.6.3.0
Other settings 1
5.7.0.0
Installation and operating instructions Wilo-Yonos GIGA-N
Operation
Type Symbol
Values/explanations
The wink function permits the identifica-
±
tion of a device in the BMS network. A
"wink" is executed by confirmation.
BMS local operation
±
BMS remote operation
Setting of bus address
±
Specific settings of the IF module, de-
±
pending on protocol type
±
±
±
Settings for sensor input 1
Display of sensor value range 1
Setting of value range; possible values:
±
0...10 V/ 2...10 V/0...20 mA/4...20 mA
ON
±
External setpoint input 2 active
OFF
External setpoint input 2 inactive
Setting of value range; possible values:
±
0...10 V/ 2...10 V/0...20 mA/4...20 mA
Settings for PID-Control
Setting of the proportional term of the
±
control
Setting of the integral term of the control
±
Setting of the derivative term of the con-
±
trol
Settings for behaviour in the event of a
fault
HV ("heating") mode
±
AC ("cooling/air-conditioning") mode
Displays emergency operation speed
Time until automatic acknowledgement of
±
an error
Display conditions
Only displayed when LON, CAN or
IF module is active
Temporary state, automatic reset
to remote operation after 5 min
Further information can be found
in the installation and operating in-
structions of the IF modules
Not displayed in constant speed
mode (incl. all sub-menus)
Not displayed with PID-Control
Setting for external setpoint in-
put 2
Not displayed when In2 = inactive
Only displayed when PID-Control is
active (incl. all sub-menus)
en